Connection guides
Wire the drive to the phone with a USB-RS485 adapter. Bench-test before you touch a production machine.
Omron 3G3MX2 over USB-RS485
- Adapter A (D+)
- to RS+ on the control terminals
- Adapter B (D-)
- to RS- on the control terminals
- Defaults
- Slave 1, 9600 baud, 8-N-1
- Termination
- Switch on the 120 ohm termination on the last drive
The RJ45 is for the remote operator only, not for ServMod. Changes to C071 to C075 apply after a power cycle.
Hitachi WJ200 and WL200
- Connection
- USB cable from the inverter, or a USB-RS485 adapter on the RS-485 terminals
- Defaults
- Slave 1, 9600 baud, 8-N-1
Allen-Bradley PowerFlex 520 and 525
- Connection
- USB-RS485 adapter on the DSI RJ45, pins 4 (TxRxD+) and 5 (TxRxD-)
- Defaults
- Node 100, 9600 baud, 8-N-1
The left RJ45 is EtherNet/IP and the right one is DSI.
If the phone does not see the adapter
- Use a data cable, not a charge-only cable, and an adapter with an FTDI, CP210x, CH34x or CH343 chip.
- Confirm the USB permission prompt when it appears.
- Check that slave number, baud rate and format in ServMod match the drive. A mismatch looks like no answer.
- Swap A and B if the drive still does not answer. Labelling differs between adapters.
Still stuck? Send the drive model and what the screen says through the support form.