Fault codes / Allen-Bradley PowerFlex 525
Allen-Bradley PowerFlex 525 fault codes: meaning and checks
47 fault and warning codes of the Allen-Bradley PowerFlex 525, each with what it means and what to check first. Tap a code for the full checklist.
| Code | Name | Meaning |
|---|---|---|
| F002 | Auxiliary input | An external trip signal wired to a digital input set as Aux Fault has opened, so the drive stopped on purpose. |
| F003 | Power loss | The drive saw a single-phase supply condition while carrying a heavy load. |
| F004 | Undervoltage | The DC bus fell below its minimum level, usually because the supply sagged or dropped out. |
| F005 | Overvoltage | The DC bus rose above its maximum level, from a high supply, line transients or motor regeneration. |
| F006 | Motor stalled | The drive could not accelerate or decelerate the motor, typically because it sat in current limit too long. |
| F007 | Motor overload | The internal electronic overload protection tripped because the motor drew excessive current for too long. |
| F008 | Heatsink overtemperature | The heatsink/power module temperature exceeded its limit. |
| F009 | Control module overtemperature | The control module temperature exceeded its limit. |
| F012 | Hardware overcurrent | Drive output current exceeded the hardware current limit. |
| F013 | Ground fault | A current path to earth was detected at one or more drive output terminals. |
| F015 | Load loss | Output torque current stayed below the A490 level for longer than A491 time, so the load appears to be lost... |
| F021 | Output phase loss | Loss of an output phase was detected (only when the function is enabled with A557). |
| F029 | Analog input loss | An analog input configured to fault on signal loss has lost its signal. |
| F033 | Auto restart tries exceeded | The drive tried to reset a fault and resume running the number of times set in A541 and did not succeed. |
| F038 | Phase U to ground | A ground fault was detected on motor phase U between the drive and the motor. |
| F039 | Phase V to ground | A ground fault was detected on motor phase V between the drive and the motor. |
| F040 | Phase W to ground | A ground fault was detected on motor phase W between the drive and the motor. |
| F041 | Phase UV short | Excessive current was detected between two output terminals (UV), indicating a short. |
| F042 | Phase UW short | Excessive current was detected between two output terminals (UW), indicating a short. |
| F043 | Phase VW short | Excessive current was detected between two output terminals (VW), indicating a short. |
| F048 | Parameters defaulted | The drive was told to write factory default values to EEPROM. |
| F059 | Safety open | Both safety inputs (Safety 1 and Safety 2) are de-energised, and t105 is set to fault in that state. |
| F063 | Software overcurrent (shear pin) | Current stayed above the shear pin level (A486/A488) for longer than the shear pin time (A487/A489). |
| F064 | Drive overload | The drive's own overload rating was exceeded. |
| F070 | Power unit | A failure was detected in the drive power section. |
| F071 | DSI network loss | Control over the Modbus/DSI (RS-485) link was interrupted. |
| F072 | Option card network loss | Control through the remote network of the optional network card was interrupted. |
| F073 | Embedded EtherNet/IP network loss | Control through the embedded EtherNet/IP adapter was interrupted. |
| F080 | Autotune failure | The autotune routine was cancelled by the user or did not complete successfully. |
| F081 | DSI communication loss | Communication between the drive and the Modbus/DSI master was interrupted. |
| F082 | Option card communication loss | Communication between the drive and the network option card was interrupted. |
| F083 | Embedded EtherNet/IP communication loss | Internal communication between the drive and the embedded EtherNet/IP adapter was interrupted. |
| F091 | Encoder loss | One of the two encoder channel signals is missing (differential encoder required). |
| F094 | Function loss | The Freeze-Fire (Function Loss) input is inactive, i.e. the input to the programmed terminal is open. |
| F100 | Parameter checksum error | The drive's non-volatile parameter storage is corrupted. |
| F101 | External storage error | External non-volatile storage has failed. |
| F105 | Control module connect error | The control module was disconnected while the drive was powered. |
| F106 | Incompatible control/power module | The PowerFlex 525 control module does not support a power module with 0.25 HP rating. |
| F107 | Replaced control/power module | The control module could not recognise the power module (hardware failure). |
| F109 | Control/power module mismatch | The control module was mounted on a different drive type of power module. |
| F110 | Keypad membrane | The keypad membrane has failed or is disconnected. |
| F111 | Safety hardware | A malfunction in the safety input enable hardware; one of the safety inputs is not enabled. |
| F114 | Microprocessor failure | Microprocessor failure. |
| F122 | I/O board failure | A failure was detected in the drive control and I/O section. |
| F125 | Flash update required | The drive firmware is corrupt, mismatched or incompatible with the hardware. |
| F126 | Non-recoverable error | A non-recoverable firmware or hardware error was detected; the drive stopped and reset itself. |
| F127 | DSI flash update required | A critical firmware problem was detected and the drive is running backup firmware that supports only DSI... |
Source: PowerFlex 520-series User Manual (520-UM001O-EN-E, September 2025). Manufacturer page. See also the Allen-Bradley PowerFlex 525 parameter list, the connection and backup page and the wiring diagrams.
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.