Fault codes / Danfoss VLT FC 280 parameters

Danfoss VLT FC 280 parameter list

244 parameters of the Danfoss VLT FC 280 with range, default value and a short description. Source: VLT Midi Drive FC 280 Programming Guide (MG07C402, 02/2019).

No.NameRangeDefaultWhat it does
0-01Language[0] English, [1] Deutsch, [2] Francais, [3] Dansk, [4] Spanish, [5] Italiano, [28] Portuguese[0] EnglishSets the language of the LCP display texts.
0-03Regional Settings[0] International, [1] North America[0] InternationalChooses kW or hp units for motor power entry (1-20) and sets the default motor frequency to 50 or 60 Hz. Cannot be changed while the motor runs.
0-04Operating State at Power-up (Hand)[0] Resume, [1] Forced stop, ref=old, [2] Forced stop, ref=0[1] Forced stop, ref=old (parameter list table shows [0] Resume)Decides how the drive behaves after mains returns when it was in Hand mode: carry on running, stay stopped with the stored local reference, or stay stopped with the local reference cleared.
0-06GridTypeSupply options by voltage class (200-240, 380-440, 440-480 V), 50/60 Hz and IT-grid / Delta / standard typeSize relatedTell the drive the actual supply voltage, frequency and earthing type. A wrong choice (especially IT grid) affects DC-link handling and overvoltage behaviour.
0-07Auto DC Braking[0] Off, [1] On[1] OnProtects against DC-link overvoltage when coasting on an IT grid. Only has effect when an IT-grid option is chosen in 0-06. Related to warning 87.
0-10Active Set-up[1] Set-up 1, [2] Set-up 2, [3] Set-up 3, [4] Set-up 4, [9] Multi Set-up[1] Set-up 1Selects which of the four parameter set-ups controls the drive. Multi set-up lets digital inputs or the bus switch set-ups remotely.
0-11Programming Set-up[1] Set-up 1 ... [4] Set-up 4, [9] Active Set-up[9] Active Set-upPicks the set-up you are editing, which may differ from the one currently running the drive.
0-12Link Setups[0] Not linked, [20] Linked[20] LinkedWhen linked, parameters that cannot be changed while running are copied between set-ups so a set-up change during operation is possible.
0-16Application Selection[0] None, [1] Simple Process Close Loop, [2] Local/Remote, [3] Speed Open Loop, [4] Simple Speed Close Loop, [5] Multi Speed, [6] OGD LA10, [7] OGD V210, [8] Hoist[0] NoneLoads a preset group of parameters for a typical application in one step. Check the resulting settings afterwards because many parameters change at once.
0-40[Hand on] Key on LCP[0] Disabled, [1] Enabled[1] EnabledEnables or blocks the Hand On key, which prevents accidental local starts when disabled.
0-42[Auto on] Key on LCP[0] Disabled, [1] Enabled[1] EnabledEnables or blocks the Auto On key on the LCP.
0-44[Off/Reset] Key on LCP[0] Disabled, [1] Enabled, [7] Enable Reset Only[1] EnabledControls whether the Off/Reset key can stop and reset the drive. Setting 7 leaves only the reset function active.
0-50LCP Copy[0] No copy, [1] All to LCP, [2] All from LCP, [3] Size indep. from LCP[0] No copyCopies parameters between the drive and the LCP. Saving to the LCP after commissioning gives you a backup, and loading from the LCP clones settings to another drive.
0-51Set-up Copy[0] No copy, [1]-[4] Copy from set-up 1-4, [9] Copy from Factory setup[0] No copyCopies a complete set-up (or the factory set-up) onto the set-up chosen in 0-11.
0-60Main Menu Password0 - 9990Protects the Main Menu with a password. Zero disables the password.
1-00Configuration Mode[0] Open Loop, [1] Speed closed loop, [2] Torque closed loop, [3] Process Closed Loop, [4] Torque open loop, [7] Extended PID Speed OL[0] Open LoopChooses the basic control principle used when a remote reference is active: plain speed control, or closed loop with feedback.
1-01Motor Control Principle[0] U/f, [1] VVC+[1] VVC+Selects the motor control method. U/f gives a simple voltage/frequency curve without slip or load compensation; VVC+ is the default vector method.
1-03Torque Characteristics[0] Constant torque, [1] Variable Torque, [2] Auto Energy Optim. CT, [3] Auto Energy Optim. VT[0] Constant torqueMatches the drive to the load type. Variable torque (fans, pumps) and the auto-energy options reduce motor magnetisation at light load to save energy.
1-06Clockwise Direction[0] Normal, [1] Inverse[0] NormalReverses the meaning of clockwise so the motor direction can be changed without swapping motor wires. Cannot be changed while running.
1-08Motor Control Bandwidth[0] High, [1] Medium, [2] Low, [3] Adaptive 1, [4] Adaptive 2[1] Medium (parameter list table says Size related)Trades dynamic response against smooth steady-state running.
1-10Motor Construction[0] Asynchron, [1] PM, non salient SPM, [3] PM, salient IPM[0] AsynchronSelects induction or permanent magnet motor type. Many other motor parameters depend on this choice.
1-20Motor PowerStandard motor ratings in kW / hp, from 0.12 kW (0.16 hp) upwardSize relatedMotor rated power from the nameplate. Together with 1-22 to 1-25 it forms the motor data the drive needs.
1-22Motor Voltage50 - 1000 VSize relatedRated motor voltage from the nameplate; check the star/delta connection that corresponds to the supply.
1-23Motor Frequency20 - 500 HzSize relatedRated motor frequency from the nameplate. For 87 Hz operation also adapt 4-14 and 3-03. Cannot be changed while running.
1-24Motor Current0.01 - 1000.00 ASize relatedRated motor current from the nameplate. It underlies torque estimation and the motor thermal protection, so a wrong value causes nuisance trips.
1-25Motor Nominal Speed50 - 60000 RPMSize relatedRated motor speed from the nameplate. Used for slip compensation and other automatic motor compensation.
1-26Motor Cont. Rated Torque0.1 - 10000.0 NmSize relatedRated continuous torque of a PM motor from its nameplate. Only available with PM motor construction.
1-29Automatic Motor Adaption (AMA)[0] Off, [1] Enable complete AMA, [2] Enable reduced AMA[0] OffStarts a self-measurement of motor parameters to tune the control. Terminal 27 must be active (not switched off with the default coast-inverse setting), and the motor should be cold. Failures show as alarms 50-58.
1-30Stator Resistance (Rs)0.0 - 9999.000 OhmSize relatedStator winding resistance, from the motor datasheet or measured by AMA on a cold motor.
1-31Rotor Resistance (Rr)0 - 9999.000 OhmSize relatedRotor resistance, from a datasheet or AMA on a cold motor. Default is calculated from nameplate data.
1-33Stator Leakage Reactance (X1)0.0 - 9999.000 OhmSize relatedStator leakage reactance, from a datasheet or AMA on a cold motor.
1-35Main Reactance (Xh)0.0 - 9999.00 OhmSize relatedMain (magnetising) reactance of the motor, found by AMA on a cold motor or from the motor datasheet.
1-37d-axis Inductance (Ld)0 - 65535 mHSize relatedd-axis inductance of a PM motor, from its datasheet or AMA on a cold motor.
1-38q-axis Inductance (Lq)0.000 - 65535 mHSize relatedq-axis inductance of a PM motor, from its datasheet or AMA on a cold motor.
1-39Motor Poles2 - 100Size relatedTotal number of motor poles (not pole pairs), always even. Needed for correct speed calculation.
1-40Back EMF at 1000 RPM1 - 9000 VSize relatedLine-to-line voltage a PM motor generates when turned externally at 1000 RPM.
1-42Motor Cable Length0 - 100 m50 mLength of the motor cable, used to compensate for cable effects. Set it correctly for long cables.
1-55U/f Characteristic - U0 - 1000 VSize relatedVoltage values at each of six frequency points of a custom U/f curve (array parameter).
1-56U/f Characteristic - F0 - 500.0 HzSize relatedFrequency points that define the custom U/f curve together with 1-55.
1-60Low Speed Load Compensation0 - 300 %100 %Adjusts voltage compensation at low speed to improve load performance. Asynchronous motors only.
1-61High Speed Load Compensation0 - 300 %100 %Adjusts voltage compensation at high speed to improve load performance. Asynchronous motors only.
1-62Slip Compensation-400 - 400.0 %Size relatedTrims slip compensation, which is calculated automatically from motor nominal speed, to allow for motor tolerance.
1-63Slip Compensation Time Constant0.05 - 5 s0.1 sReaction speed of slip compensation. Raise it if low-frequency resonance or hunting appears.
1-64Resonance Dampening0 - 500 %100 %Damps high-frequency resonance of the motor; increase to reduce oscillation, in step with 1-65.
1-66Min. Current at Low Speed0 - 120 %50 %Minimum motor current at low speed; raising it increases low-speed torque. Only active for PM motors.
1-70Start Mode[0] Rotor Detection, [1] Parking, [3] Rotor Last Position[0] Rotor DetectionStart-up method for PM motors in VVC+, used when the motor may be free-running or stopped.
1-71Start Delay0.0 - 10.0 s0 sDelays the start of acceleration. The function used during the delay is chosen in 1-72.
1-72Start Function[0] DC Hold/delay time, [1] DC-Brake/delay time, [2] Coast/delay time, [3] Start speed cw, [4] Horizontal operation, [5] VVC+ clockwise[2] Coast/delay timeChooses what the drive does during the start delay: DC hold, DC brake, coast, or special start-speed functions for hoists and cone-rotor motors.
1-75Start Speed [Hz]0 - 500.0 HzSize relatedFrequency the output jumps to at start when a start-speed function is selected in 1-72.
1-76Start Current0 - 1000 ASize relatedExtra current used at start with start-speed functions, for motors needing help to break away (e.g. cone rotor).
1-80Function at Stop[0] Coast, [1] DC hold / Motor Preheat, [3] Pre-magnetizing (options depend on motor construction)[0] CoastChooses what the drive does after a stop command once speed has fallen to the level in 1-82.
1-82Min Speed for Function at Stop [Hz]0 - 20 Hz0 HzOutput frequency below which the function chosen in 1-80 becomes active.
1-88AC Brake Gain1.0 - 2.01.4Strength of the AC brake. Higher values brake harder; 1.0 means no AC brake capability.
1-90Motor Thermal Protection[0] No protection, [1] Thermistor warning, [2] Thermistor trip, [3] ETR warning 1, [4] ETR trip 1, [22] ETR Trip - Extended Delay[0] No protectionSelects how the motor is protected against overheating: using a PTC thermistor, or the drive's electronic thermal model. Leaving it at 0 gives no protection.
1-93Thermistor Source[0] None, [1] Analog Input 53, [2] Analog Input 54, [3] Digital input 18, [4] Digital input 19, [5] Digital input 32, [6] Digital input 33[0] NoneTells the drive which terminal the motor PTC thermistor is wired to. Set the matching input mode first (5-00, 6-19, 6-29).
2-00DC Hold/Motor Preheat Current0 - 160 %50 %Holding current for DC hold or motor preheating, as a percentage of rated motor current.
2-01DC Brake Current0 - 150 %50 %Braking current for DC brake, as a percentage of rated motor current.
2-02DC Braking Time0 - 60 s10 sHow long DC brake current is applied after a stop. A value of 0 disables DC braking.
2-04DC Brake Cut In Speed0 - 500 Hz0 HzFrequency at which DC braking is switched in during a stop.
2-10Brake Function[0] Off, [1] Resistor brake, [2] AC brake[0] OffSelects how regenerative energy is dealt with: no brake, a brake resistor, or AC braking.
2-11Brake Resistor (ohm)0 - 6200 OhmSize relatedValue of the connected brake resistor, used to monitor brake power.
2-12Brake Power Limit (kW)0.001 - 2000 kWSize relatedMaximum power the brake resistor may dissipate, monitored over a 120 s window (see warning 26).
2-16AC Brake, Max current0 - 160 %100 %Current limit during AC braking.
2-17Over-voltage Control[0] Disabled, [1] Enabled (not at stop), [2] Enabled[0] DisabledLets the drive stretch the deceleration ramp automatically to avoid DC-link overvoltage trips.
2-19Over-voltage Gain0 - 200 %100 %Tunes how strongly the over-voltage control reacts.
2-20Release Brake Current0 - 100 A0 AMotor current that must be reached before a mechanical brake is released.
2-22Activate Brake Speed [Hz]0 - 400 Hz0 HzFrequency at which the mechanical brake is applied during stopping.
2-23Activate Brake Delay0 - 5 s0 sDelay before the mechanical brake is applied after stopping.
3-00Reference Range[0] Min - Max, [1] -Max - +Max[0] Min - MaxSelects whether references may be only positive or both positive and negative.
3-02Minimum Reference-4999.000 - 4999.000 reference units0Lowest reference value obtainable from all sources; defines the minimum speed or process value.
3-03Maximum Reference-4999.0 - 4999 reference/feedback unitsSize relatedHighest reference value obtainable by summing all references.
3-04Reference Function[0] Sum, [1] External/Preset[0] SumEither adds external and preset references together or switches between them with a command or digital input.
3-10Preset Reference-100 - 100 % (array of 8)0 %Up to eight fixed references, selected by digital inputs or the bus, expressed as a percentage of the reference range.
3-11Jog Speed [Hz]0 - 500.0 Hz5 HzFixed output frequency used while jog is active.
3-14Preset Relative Reference-100 - 100 %0 %Defines a percentage added to the actual reference to give a relative reference.
3-15Reference 1 Source[0] No function, [1] Analog Input 53, [2] Analog Input 54, [7] Frequency input 29, [8] Frequency input 33, [11] Local bus reference, [20] Digital pot.meter, [32] Bus PCD[1] Analog Input 53Chooses the first source of the speed/process reference.
3-16Reference 2 SourceSame options as 3-15[2] Analog Input 54Chooses the second reference source.
3-17Reference 3 SourceSame options as 3-15[11] Local bus referenceChooses the third reference source.
3-41Ramp 1 Ramp Up Time0.01 - 3600 sSize relatedAcceleration time from 0 to the rated motor frequency (1-23). Too short a time can cause current limit or overcurrent.
3-42Ramp 1 Ramp Down Time0.01 - 3600 sSize relatedDeceleration time from rated motor frequency to 0. Too short a time can cause DC overvoltage unless a brake is fitted.
3-51Ramp 2 Ramp Up Time0.01 - 3600 sSize relatedAcceleration time for the second ramp, selectable by digital input.
3-52Ramp 2 Ramp Down Time0.01 - 3600 sSize relatedDeceleration time for the second ramp.
3-80Jog Ramp Time0.01 - 3600 sSize relatedRamp time used when jogging.
3-81Quick Stop Ramp Time0.01 - 3600 sSize relatedDeceleration time used for a quick stop command.
4-10Motor Speed Direction[0] Clockwise, [2] Both[0] ClockwiseAllowed rotation directions. Must allow both directions if reversing is to be used.
4-12Motor Speed Low Limit [Hz]0 - 400.0 Hz0 HzMinimum output frequency during operation.
4-14Motor Speed High Limit [Hz]0.1 - 500 Hz65 HzMaximum output frequency the motor is allowed to run at; set it with the mechanical limits of the machine in mind.
4-16Torque Limit Motor Mode0 - 1000 %Size relatedTorque limit when driving the load. Reaching it gives warning/alarm 12.
4-17Torque Limit Generator Mode0 - 1000 %100 %Torque limit when the load drives the motor (regenerating).
4-18Current Limit0 - 1000 %Size relatedOutput current limit. Reaching it gives warning/alarm 59.
4-19Max Output Frequency0 - 500 HzSize relatedAbsolute upper limit on drive output frequency regardless of other settings; cannot exceed 10% of the switching frequency.
4-20Torque Limit Factor Source[0] No function, [2] Analog in 53, [4] Analog in 53 inv, [6] Analog in 54, [8] Analog in 54 inv, [18] Bus Control[0] No functionScales the torque limits with an analog input or the bus.
4-22Break Away Boost[0] Off, [1] On[0] OffProvides extra starting torque for loads that are hard to break away.
4-30Motor Feedback Loss Function[0] Disabled, [1] Warning, [2] Trip, [3] Jog, [4] Freeze Output, [5] Max Speed, [6] Switch to Open Loop[2] TripWhat to do if the feedback signal is lost in closed-loop speed control.
4-40Warning Freq. Low0 - 500 HzSize relatedFrequency below which a low-frequency warning is issued.
4-41Warning Freq. High0 - 500 HzSize relatedFrequency above which a high-frequency warning is issued.
4-50Warning Current Low0 - 500 A0 AMotor current below which a low-current warning is issued; useful for detecting a lost load.
4-51Warning Current High0.0 - 500.00 ASize relatedMotor current above which a high-current warning is issued.
4-58Missing Motor Phase Function[0] Off, [1] On[1] OnEnables detection of a missing motor phase, giving alarms 30-32.
4-61Bypass Speed From [Hz]0 - 500 Hz0 HzStart of a speed band the drive skips over to avoid mechanical resonance.
4-63Bypass Speed To [Hz]0 - 500 Hz0 HzEnd of the skipped speed band.
5-00Digital Input Mode[0] PNP, [1] NPN[0] PNPSets the wiring logic of the digital inputs (PNP active at 24 V, NPN active at 0 V). Wrong setting makes inputs seem dead.
5-01Terminal 27 Mode[0] Input, [1] Output[0] InputSelects whether terminal 27 acts as a digital input or output.
5-10Terminal 18 Digital InputFunction list: [0] No operation, [1] Reset, [2] Coast inverse, [3] Coast and reset inverse, [4] Quick stop inverse, [5] DC-brake inverse, [6] Stop inverse, [8] Start, [9] Latched start, [10] Reversing, [11] Start reversing, [14] Jog, [15] Preset reference on, [16-18] Preset ref bit 0-2 and more[8] StartAssigns a function to terminal 18. The same function list applies to all digital inputs 5-10 to 5-15.
5-11Terminal 19 Digital InputSame function list as 5-10[10] ReversingAssigns a function to terminal 19.
5-12Terminal 27 Digital InputSame function list as 5-10[2] Coast inverseAssigns a function to terminal 27 (when set as input). Coast inverse by default means the terminal must be live for the drive to run, and AMA cannot run if it is off.
5-13Terminal 29 Digital InputSame function list as 5-10 plus [32] Pulse input[14] JogAssigns a function to terminal 29.
5-14Terminal 32 Digital InputSame function list as 5-10 plus encoder input B[0] No operationAssigns a function to terminal 32.
5-15Terminal 33 Digital InputSame function list as 5-10 plus [32] Pulse input and encoder input A[16] Preset ref bit 0Assigns a function to terminal 33.
5-19Terminal 37/38 Safe Torque Off[1] Safe Torque Off Alarm, [3] Safe Torque Off Warning[1] Safe Torque Off AlarmSets how the drive reacts when STO is triggered: alarm 68 or warning 68, and whether restart is manual or automatic.
5-30Terminal 27 Digital OutputSame function list as 5-40 (e.g. [1] Control ready, [2] Drive ready, [5] Running)[0] No operationAssigns a status function to terminal 27 when used as a digital output.
5-40Function Relay[0] No operation, [1] Control Ready, [2] Drive ready, [3] Drive rdy/remote, [4] Stand-by / no warning, [5] Running, [6] Running / no warning, and many further status functionsSize relatedSelects which drive condition (ready, running, alarm, warning, etc.) switches the relay output. Array with one element per relay.
5-41On Delay, Relay0 - 600 s0.01 sDelay before the relay closes after its condition becomes true.
5-42Off Delay, Relay0 - 600 s0.01 sDelay before the relay opens after its condition becomes false.
5-50Term. 29 Low Frequency0 - 31999 Hz4 HzLow end of the pulse frequency range on terminal 29, matched to the low reference/feedback value.
5-51Term. 29 High Frequency1 - 32000 Hz32000 HzHigh end of the pulse frequency range on terminal 29.
5-55Term. 33 Low Frequency0 - 31999 Hz4 HzLow end of the pulse frequency range on terminal 33.
5-56Term. 33 High Frequency1 - 32000 Hz32000 HzHigh end of the pulse frequency range on terminal 33.
6-00Live Zero Timeout Time1 - 99 s10 sHow long an analog signal must stay below its live-zero level before the reaction in 6-01 occurs.
6-01Live Zero Timeout Function[0] Off, [1] Freeze output, [2] Stop, [3] Jogging, [4] Max. speed, [5] Stop and trip[0] OffReaction when an analog reference signal is lost (live zero error, warning/alarm 2).
6-10Terminal 53 Low Voltage0 - 10 V0.07 VVoltage on terminal 53 that corresponds to the low reference value. Also the basis for live-zero detection.
6-11Terminal 53 High Voltage0 - 10 V10 VVoltage on terminal 53 that corresponds to the high reference value.
6-14Terminal 53 Low Ref./Feedb. Value-4999 - 49990Reference or feedback value corresponding to the low voltage on terminal 53.
6-15Terminal 53 High Ref./Feedb. Value-4999 - 4999Size relatedReference or feedback value corresponding to the high voltage on terminal 53.
6-16Terminal 53 Filter Time Constant0.01 - 10 s0.01 sLow-pass filter on the terminal 53 signal to damp noise; longer means slower response.
6-19Terminal 53 mode[1] Voltage mode, [6] Digital input[1] Voltage modeSets terminal 53 as an analog voltage input or as a digital input (e.g. for a thermistor).
6-20Terminal 54 Low Voltage0 - 10 V0.07 VVoltage on terminal 54 that corresponds to the low reference value.
6-21Terminal 54 High Voltage0 - 10 V10 VVoltage on terminal 54 that corresponds to the high reference value.
6-22Terminal 54 Low Current0 - 20 mA4 mACurrent on terminal 54 that corresponds to the low reference value. A 4-20 mA loop below 2 mA triggers live zero.
6-23Terminal 54 High Current0 - 20 mA20 mACurrent on terminal 54 that corresponds to the high reference value.
6-24Terminal 54 Low Ref./Feedb. Value-4999 - 49990Reference or feedback value corresponding to the low signal on terminal 54.
6-25Terminal 54 High Ref./Feedb. Value-4999 - 4999Size relatedReference or feedback value corresponding to the high signal on terminal 54.
6-26Terminal 54 Filter Time Constant0.01 - 10 s0.01 sLow-pass filter on the terminal 54 signal.
6-29Terminal 54 mode[0] Current mode, [1] Voltage mode[1] Voltage modeSets terminal 54 for current or voltage input. It must match the actual signal and the hardware switch setting.
6-90Terminal 42 Mode[0] 0-20 mA, [1] 4-20 mA, [2] Digital Output[0] 0-20 mASelects the signal type of terminal 42.
6-91Terminal 42 Analog Output[0] No operation, [100] Output frequency, [101] Reference, [102] Process Feedback, [103] Motor Current, [104] Torque rel to limit, [105] Torq relate to rated, [106] Power, [107] Speed, [111] Speed Feedback, [113] PID Clamped Output, [139] Bus Control, [143] Ext. CL, [254] DC Link Voltage[0] No operationChooses which drive value is sent on the analog output terminal 42.
7-00Speed PID Feedback Source[1] 24V encoder, [6] Analog Input 53, [7] Analog Input 54, [8] Frequency input 29, [9] Frequency input 33, [20] None[20] NoneSelects the feedback device for closed-loop speed control.
7-20Process CL Feedback 1 Resource[0] No function, [1] Analog Input 53, [2] Analog Input 54, [3] Frequency input 29, [4] Frequency input 33[0] No functionChooses the input that provides feedback for process closed loop control.
7-30Process PID Normal/ Inverse Control[0] Normal, [1] Inverse[0] NormalNormal raises output when feedback is below setpoint; inverse lowers output in that case (e.g. cooling).
7-33Process PID Proportional Gain0 - 100.01Proportional gain of the process PID: how strongly the output reacts to the error.
7-34Process PID Integral Time0.10 - 9999 s9999 sIntegral time of the process PID; shorter is faster correction but more risk of overshoot. 9999 effectively disables it.
7-35Process PID Differentiation Time0 - 20 s0 sDifferentiation time of the process PID, rarely needed.
8-01Control Site[0] Digital and ctrl.word, [1] Digital only, [2] Controlword only[0] Digital and ctrl.wordChooses whether control comes from digital inputs, the fieldbus control word or both. Overrides the select parameters 8-50 to 8-58.
8-02Control Source[0] None, [1] FC Port, [2] FC USB, [3] Option ASize relatedSelects the interface the control word and bus reference are accepted from.
8-03Control Timeout Time0.5 - 6000 s1 sMaximum time allowed between control messages; if exceeded the function in 8-04 is executed.
8-04Control Timeout Function[0] Off, [1] Freeze output, [2] Stop, [3] Jogging, [4] Max. speed, [5] Stop and trip[0] OffReaction when serial communication times out (warning/alarm 17).
8-10Control Word Profile[0] FC profile, [1] PROFIdrive profile, [5] ODVA, [7] CANopen DSP 402[0] FC profileSelects the control and status word profile used by the fieldbus.
8-30Protocol[0] FC, [2] Modbus RTU[0] FCSelects the protocol on the RS485 port. Choose Modbus RTU for Modbus masters.
8-31Address0 - 2471Station address of the drive on the serial bus.
8-32Baud Rate[0] 2400, [1] 4800, [2] 9600, [3] 19200, [4] 38400, [5] 57600, [6] 76800, [7] 115200 BaudSize relatedSerial communication speed; must match the master.
8-33Parity / Stop Bits[0] Even, 1 stop bit, [1] Odd, 1 stop bit, [2] No parity, 1 stop bit, [3] No parity, 2 stop bitsSize relatedParity and stop bit format of the serial port; must match the master.
8-35Minimum Response Delay0.0010 - 0.5 s0.01 sMinimum pause before the drive answers a serial request, for slow masters.
8-36Maximum Response Delay0.1 - 10.0 sSize relatedMaximum time the drive may take to answer a request.
8-50Coasting Select[0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR[3] Logic ORChooses whether coast is triggered by a digital input, the bus, or a combination. The other 8-5* parameters work in the same way.
8-51Quick Stop Select[0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR[3] Logic ORSelects the source of the quick stop command.
8-53Start Select[0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR[3] Logic ORSelects the source of the start command.
8-54Reversing Select[0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR[3] Logic ORSelects the source of the reverse command.
8-56Preset Reference Select[0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR[3] Logic ORSelects the source of the preset reference selection.
8-80Bus Message Count0 - 42949672950Counter of valid messages seen on the bus; read-only diagnostic.
8-81Bus Error Count0 - 42949672950Counter of messages with errors; useful to detect noise or wrong settings.
8-82Slave Messages Rcvd0 - 42949672950Number of valid messages addressed to this drive.
8-83Slave Error Count0 - 42949672950Number of messages the drive could not execute.
8-85Slave Timeout Errors0 - 42949672950Number of times a slave message timed out.
8-88Reset FC port Diagnostics[0] Do not reset, [1] Reset counter[0] Do not resetClears the bus diagnostic counters in 8-80 to 8-85.
14-01Switching Frequency[0] Ran3, [1] Ran5, [2] 2.0 kHz, [3] 3.0, [4] 4.0, [5] 5.0, [6] 6.0, [7] 8.0, [8] 10.0, [9] 12.0, [10] 16.0 kHzSize relatedInverter carrier frequency. Higher values mean quieter motor but more drive heating and derating; lower values mean less heat.
14-03Overmodulation[0] Off, [1] On[1] OnAllows the output voltage to rise above normal for more motor voltage at high speed, at the cost of torque ripple.
14-10Mains Failure[0] No function, [1] Ctrl. ramp-down, [2] Ctrl. ramp-down and trip, [3] Coasting, [4]-[7] kinetic back-up and alarm variants[0] No functionDefines how the drive reacts to a short supply dip once the voltage falls to the level in 14-11: ignore it, ramp down under control, coast, or use kinetic back-up. Cannot be changed while the motor runs.
14-11Mains Fault Voltage Level100 - 800 VSize relatedSupply voltage threshold at which the mains failure function in 14-10 starts (alarm/warning 36).
14-12Function at Mains Imbalance[0] Trip, [1] Warning, [2] Disabled[0] TripReaction to severe supply voltage imbalance or phase loss.
14-20Reset Mode[0] Manual reset, [1]-[10] Automatic reset x1...x10, [11] x15, [12] x20, [13] Infinite auto reset, [14] Reset at power-up[0] Manual resetChooses whether trips are reset manually or automatically after a trip. Automatic reset can restart the motor without warning, so use with care. Does not apply to alarms 68 and 188.
14-21Automatic Restart Time0 - 600 s10 sDelay between a trip and the automatic reset attempt.
14-22Operation Mode[0] Normal operation, [2] Initialisation[0] Normal operationSet to Initialisation to restore factory defaults; the reset takes effect at the next power-up.
14-24Trip Delay at Current Limit0 - 60 s60 sTime the drive can run at current limit before tripping. 60 means no trip.
14-25Trip Delay at Torque Limit0 - 60 s60 sTime the drive can run at torque limit before tripping. 60 means no trip.
14-27Action At Inverter Fault[0] Trip, [1] Warning[1] WarningChooses how the drive reacts to overvoltage or ground-fault conditions: Trip disables the protection filters and trips at the first fault, Warning keeps the protection filters running.
14-28Production Settings[0] No action, [1] Service reset, [3] Software Reset[0] No actionService-oriented function for resets; leave at no action in normal use.
14-29Service Code0 - 0x7FFFFFFF0Only for use by service technicians.
14-40VT Level40 - 90 %66 %Magnetisation level used in variable torque operation (see 1-03).
14-52Fan Control[5] Constant-on mode, [6] Constant-off mode, [7] On-when-Inverter-is-on, [8] Variable-speed mode[8] Variable-speed modeSelects how the internal cooling fan is controlled.
14-55Output Filter[0] No Filter, [1] Sine-Wave Filter[0] No FilterTells the drive that a sine-wave filter is fitted on the output so it can adjust its operation accordingly.
14-61Function at Inverter Overload[0] Trip, [1] Derate[0] TripChooses whether inverter overload trips the drive or reduces output (derating).
14-90Fault LevelPer alarm: [0] Off, [3] Trip Lock, [4] Trip w. delayed reset, [5] Flystart[3] Trip LockLets you change the severity of selected alarms (such as ground fault or overcurrent) to trip lock, delayed-reset trip or similar.
15-00Operating hours0 - 0x7fffffff h0 hTotal hours the drive has been powered up.
15-01Running Hours0 - 0x7fffffff h0 hTotal hours the motor has been running.
15-02kWh Counter0 - 2147483647 kWh0 kWhAccumulated energy consumption of the motor.
15-03Power Up's0 - 21474836470Number of times the drive has been powered up.
15-04Over Temp's0 - 655350Number of times the drive has had an over-temperature fault.
15-05Over Volt's0 - 655350Number of times the drive has had a DC overvoltage fault.
15-06Reset kWh Counter[0] Do not reset, [1] Reset counter[0] Do not resetResets the kWh counter (15-02).
15-07Reset Running Hours Counter[0] Do not reset, [1] Reset counter[0] Do not resetResets the running hours counter (15-01).
15-30Alarm Log: Error Code0 - 255 (array)0History of recent alarm codes; the newest entries are first. Use it to see what tripped the drive.
15-31InternalFaultReason-32767 - 327670Extra code describing an internal fault; give it to the supplier when reporting alarm 38.
15-40FC Typetext0Drive type designation.
15-41Power Sectiontext0Power section designation of the drive.
15-42Voltagetext0Voltage class of the power section.
15-43Software Versiontext0Installed software version.
15-46Drive Ordering Notext0Ordering number of the drive.
15-51Frequency Converter Serial Numbertext0Serial number of the drive.
16-00Control Word0 - 655350Control word last received from the bus or terminals, shown in hex.
16-01Reference [Unit]-4999 - 4999 reference/feedback units0Present reference in the selected reference unit.
16-03Status Word0 - 655350Current drive status word, in hex.
16-05Main Actual Value [%]-200 - 200 %0 %The main actual value word sent with the status word, as a percentage.
16-10Power [kW]0 - 1000 kW0 kWPresent motor power in kW.
16-12Motor Voltage0 - 65535 V0 VVoltage supplied to the motor.
16-13Frequency0 - 6553.5 Hz0 HzPresent output frequency (without resonance dampening).
16-14Motor current0 - 655.35 A0 APresent motor current.
16-15Frequency [%]0 - 6553.5 %0 %Output frequency as a percentage of the maximum frequency.
16-17Speed [RPM]-30000 - 30000 RPM0 RPMActual motor speed.
16-18Motor Thermal0 - 100 %0 %Calculated thermal load of the motor; around 100% triggers the ETR protection.
16-22Torque [%]-200 - 200 %0 %Present torque as a percentage of the rated motor torque.
16-30DC Link Voltage0 - 65535 V0 VPresent DC-link voltage; useful when diagnosing alarms 7 and 8.
16-33Brake Energy Average0 - 10000 kW0 kWAverage power sent to the brake resistor.
16-34Heatsink Temp.-128 - 127 deg C0 deg CPresent heatsink temperature.
16-35Inverter Thermal0 - 255 %0 %Calculated thermal load of the inverter.
16-36Inv. Nom. Current0 - 655.35 Aread-onlyNominal current of the inverter.
16-37Inv. Max. Current0 - 655.35 Aread-onlyMaximum current of the inverter.
16-39Control Card Temp.0 - 65535 deg C0 deg CPresent control card temperature.
16-52Feedback[Unit]-4999 - 4999 process units0Feedback value in the selected process unit.
16-60Digital Input0 - 40950Binary state of the digital inputs, useful for checking wiring.
16-61Terminal 53 Setting[1] Voltage mode, [6] Digital inputSize relatedShows whether terminal 53 is set to voltage or digital input.
16-62Analog input 530 - 201Present value on analog input 53.
16-63Terminal 54 Setting[0] Current mode, [1] Voltage modeSize relatedShows whether terminal 54 is set to current or voltage.
16-64Analog input 540 - 201Present value on analog input 54.
16-65Analog output 42 [mA]0 - 20 mA0 mAPresent current on analog output 42.
16-66Digital Output0 - 630Binary state of the digital outputs.
16-71Relay output0 - 310Binary state of the relay outputs.
16-82Fieldbus REF 1-32768 - 327670Reference word last received from the fieldbus, for checking communication.
16-90Alarm Word0 - 0xFFFFFFFF0Alarm word in hex; bits map to active alarms (see Table 6.3).
16-91Alarm Word 20 - 0xFFFFFFFF0Second alarm word in hex.
16-92Warning Word0 - 0xFFFFFFFF0Warning word in hex; bits map to active warnings.
16-93Warning Word 20 - 0xFFFFFFFF0Second warning word in hex.
16-94Ext. Status Word0 - 0xFFFFFFFF0Extended status word with running states such as ramping, braking, sleep.
16-95Ext. Status Word 20 - 0xFFFFFFFF0Second extended status word.
16-97Alarm Word 30 - 0xFFFFFFFF0Third alarm word in hex.
16-98Warning Word 30 - 42949672950Third warning word in hex.
22-40Minimum Run Time0 - 600 s10 sMinimum time the motor runs after a start in sleep mode, to avoid short cycling.
22-41Minimum Sleep Time0 - 600 s10 sMinimum time the drive stays in sleep before waking.
22-43Wake-Up Speed [Hz]0 - 400.0 Hz10Speed above which the drive wakes from sleep when in open loop.
22-44Wake-Up Ref./FB Diff0 - 100 %10 %Difference between reference and feedback that wakes the drive from sleep in closed loop.
22-60Broken Belt Function[0] Off, [1] Warning, [2] Trip[0] OffReaction when load torque falls below the broken belt torque (22-61) for the delay in 22-62.
22-61Broken Belt Torque5 - 100 %10 %Torque level below which a broken belt is assumed.
22-62Broken Belt Delay0 - 600 s10 sTime torque must stay low before the broken belt reaction occurs.
30-22Locked Rotor Protection[0] Off, [1] On[0] OffEnables locked-rotor detection (alarm 99).
30-23Locked Rotor Detection Time [s]0.05 - 1 s0.10 sTime the locked condition must persist before alarm 99 is raised.

See also the Danfoss VLT FC 280 fault codes. ServMod reads, compares and backs up these parameters from your phone: how to connect.

Download free for Android

This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.