Fault codes / Danfoss VLT FC 280 parameters
Danfoss VLT FC 280 parameter list
244 parameters of the Danfoss VLT FC 280 with range, default value and a short description. Source: VLT Midi Drive FC 280 Programming Guide (MG07C402, 02/2019).
| No. | Name | Range | Default | What it does |
|---|---|---|---|---|
| 0-01 | Language | [0] English, [1] Deutsch, [2] Francais, [3] Dansk, [4] Spanish, [5] Italiano, [28] Portuguese | [0] English | Sets the language of the LCP display texts. |
| 0-03 | Regional Settings | [0] International, [1] North America | [0] International | Chooses kW or hp units for motor power entry (1-20) and sets the default motor frequency to 50 or 60 Hz. Cannot be changed while the motor runs. |
| 0-04 | Operating State at Power-up (Hand) | [0] Resume, [1] Forced stop, ref=old, [2] Forced stop, ref=0 | [1] Forced stop, ref=old (parameter list table shows [0] Resume) | Decides how the drive behaves after mains returns when it was in Hand mode: carry on running, stay stopped with the stored local reference, or stay stopped with the local reference cleared. |
| 0-06 | GridType | Supply options by voltage class (200-240, 380-440, 440-480 V), 50/60 Hz and IT-grid / Delta / standard type | Size related | Tell the drive the actual supply voltage, frequency and earthing type. A wrong choice (especially IT grid) affects DC-link handling and overvoltage behaviour. |
| 0-07 | Auto DC Braking | [0] Off, [1] On | [1] On | Protects against DC-link overvoltage when coasting on an IT grid. Only has effect when an IT-grid option is chosen in 0-06. Related to warning 87. |
| 0-10 | Active Set-up | [1] Set-up 1, [2] Set-up 2, [3] Set-up 3, [4] Set-up 4, [9] Multi Set-up | [1] Set-up 1 | Selects which of the four parameter set-ups controls the drive. Multi set-up lets digital inputs or the bus switch set-ups remotely. |
| 0-11 | Programming Set-up | [1] Set-up 1 ... [4] Set-up 4, [9] Active Set-up | [9] Active Set-up | Picks the set-up you are editing, which may differ from the one currently running the drive. |
| 0-12 | Link Setups | [0] Not linked, [20] Linked | [20] Linked | When linked, parameters that cannot be changed while running are copied between set-ups so a set-up change during operation is possible. |
| 0-16 | Application Selection | [0] None, [1] Simple Process Close Loop, [2] Local/Remote, [3] Speed Open Loop, [4] Simple Speed Close Loop, [5] Multi Speed, [6] OGD LA10, [7] OGD V210, [8] Hoist | [0] None | Loads a preset group of parameters for a typical application in one step. Check the resulting settings afterwards because many parameters change at once. |
| 0-40 | [Hand on] Key on LCP | [0] Disabled, [1] Enabled | [1] Enabled | Enables or blocks the Hand On key, which prevents accidental local starts when disabled. |
| 0-42 | [Auto on] Key on LCP | [0] Disabled, [1] Enabled | [1] Enabled | Enables or blocks the Auto On key on the LCP. |
| 0-44 | [Off/Reset] Key on LCP | [0] Disabled, [1] Enabled, [7] Enable Reset Only | [1] Enabled | Controls whether the Off/Reset key can stop and reset the drive. Setting 7 leaves only the reset function active. |
| 0-50 | LCP Copy | [0] No copy, [1] All to LCP, [2] All from LCP, [3] Size indep. from LCP | [0] No copy | Copies parameters between the drive and the LCP. Saving to the LCP after commissioning gives you a backup, and loading from the LCP clones settings to another drive. |
| 0-51 | Set-up Copy | [0] No copy, [1]-[4] Copy from set-up 1-4, [9] Copy from Factory setup | [0] No copy | Copies a complete set-up (or the factory set-up) onto the set-up chosen in 0-11. |
| 0-60 | Main Menu Password | 0 - 999 | 0 | Protects the Main Menu with a password. Zero disables the password. |
| 1-00 | Configuration Mode | [0] Open Loop, [1] Speed closed loop, [2] Torque closed loop, [3] Process Closed Loop, [4] Torque open loop, [7] Extended PID Speed OL | [0] Open Loop | Chooses the basic control principle used when a remote reference is active: plain speed control, or closed loop with feedback. |
| 1-01 | Motor Control Principle | [0] U/f, [1] VVC+ | [1] VVC+ | Selects the motor control method. U/f gives a simple voltage/frequency curve without slip or load compensation; VVC+ is the default vector method. |
| 1-03 | Torque Characteristics | [0] Constant torque, [1] Variable Torque, [2] Auto Energy Optim. CT, [3] Auto Energy Optim. VT | [0] Constant torque | Matches the drive to the load type. Variable torque (fans, pumps) and the auto-energy options reduce motor magnetisation at light load to save energy. |
| 1-06 | Clockwise Direction | [0] Normal, [1] Inverse | [0] Normal | Reverses the meaning of clockwise so the motor direction can be changed without swapping motor wires. Cannot be changed while running. |
| 1-08 | Motor Control Bandwidth | [0] High, [1] Medium, [2] Low, [3] Adaptive 1, [4] Adaptive 2 | [1] Medium (parameter list table says Size related) | Trades dynamic response against smooth steady-state running. |
| 1-10 | Motor Construction | [0] Asynchron, [1] PM, non salient SPM, [3] PM, salient IPM | [0] Asynchron | Selects induction or permanent magnet motor type. Many other motor parameters depend on this choice. |
| 1-20 | Motor Power | Standard motor ratings in kW / hp, from 0.12 kW (0.16 hp) upward | Size related | Motor rated power from the nameplate. Together with 1-22 to 1-25 it forms the motor data the drive needs. |
| 1-22 | Motor Voltage | 50 - 1000 V | Size related | Rated motor voltage from the nameplate; check the star/delta connection that corresponds to the supply. |
| 1-23 | Motor Frequency | 20 - 500 Hz | Size related | Rated motor frequency from the nameplate. For 87 Hz operation also adapt 4-14 and 3-03. Cannot be changed while running. |
| 1-24 | Motor Current | 0.01 - 1000.00 A | Size related | Rated motor current from the nameplate. It underlies torque estimation and the motor thermal protection, so a wrong value causes nuisance trips. |
| 1-25 | Motor Nominal Speed | 50 - 60000 RPM | Size related | Rated motor speed from the nameplate. Used for slip compensation and other automatic motor compensation. |
| 1-26 | Motor Cont. Rated Torque | 0.1 - 10000.0 Nm | Size related | Rated continuous torque of a PM motor from its nameplate. Only available with PM motor construction. |
| 1-29 | Automatic Motor Adaption (AMA) | [0] Off, [1] Enable complete AMA, [2] Enable reduced AMA | [0] Off | Starts a self-measurement of motor parameters to tune the control. Terminal 27 must be active (not switched off with the default coast-inverse setting), and the motor should be cold. Failures show as alarms 50-58. |
| 1-30 | Stator Resistance (Rs) | 0.0 - 9999.000 Ohm | Size related | Stator winding resistance, from the motor datasheet or measured by AMA on a cold motor. |
| 1-31 | Rotor Resistance (Rr) | 0 - 9999.000 Ohm | Size related | Rotor resistance, from a datasheet or AMA on a cold motor. Default is calculated from nameplate data. |
| 1-33 | Stator Leakage Reactance (X1) | 0.0 - 9999.000 Ohm | Size related | Stator leakage reactance, from a datasheet or AMA on a cold motor. |
| 1-35 | Main Reactance (Xh) | 0.0 - 9999.00 Ohm | Size related | Main (magnetising) reactance of the motor, found by AMA on a cold motor or from the motor datasheet. |
| 1-37 | d-axis Inductance (Ld) | 0 - 65535 mH | Size related | d-axis inductance of a PM motor, from its datasheet or AMA on a cold motor. |
| 1-38 | q-axis Inductance (Lq) | 0.000 - 65535 mH | Size related | q-axis inductance of a PM motor, from its datasheet or AMA on a cold motor. |
| 1-39 | Motor Poles | 2 - 100 | Size related | Total number of motor poles (not pole pairs), always even. Needed for correct speed calculation. |
| 1-40 | Back EMF at 1000 RPM | 1 - 9000 V | Size related | Line-to-line voltage a PM motor generates when turned externally at 1000 RPM. |
| 1-42 | Motor Cable Length | 0 - 100 m | 50 m | Length of the motor cable, used to compensate for cable effects. Set it correctly for long cables. |
| 1-55 | U/f Characteristic - U | 0 - 1000 V | Size related | Voltage values at each of six frequency points of a custom U/f curve (array parameter). |
| 1-56 | U/f Characteristic - F | 0 - 500.0 Hz | Size related | Frequency points that define the custom U/f curve together with 1-55. |
| 1-60 | Low Speed Load Compensation | 0 - 300 % | 100 % | Adjusts voltage compensation at low speed to improve load performance. Asynchronous motors only. |
| 1-61 | High Speed Load Compensation | 0 - 300 % | 100 % | Adjusts voltage compensation at high speed to improve load performance. Asynchronous motors only. |
| 1-62 | Slip Compensation | -400 - 400.0 % | Size related | Trims slip compensation, which is calculated automatically from motor nominal speed, to allow for motor tolerance. |
| 1-63 | Slip Compensation Time Constant | 0.05 - 5 s | 0.1 s | Reaction speed of slip compensation. Raise it if low-frequency resonance or hunting appears. |
| 1-64 | Resonance Dampening | 0 - 500 % | 100 % | Damps high-frequency resonance of the motor; increase to reduce oscillation, in step with 1-65. |
| 1-66 | Min. Current at Low Speed | 0 - 120 % | 50 % | Minimum motor current at low speed; raising it increases low-speed torque. Only active for PM motors. |
| 1-70 | Start Mode | [0] Rotor Detection, [1] Parking, [3] Rotor Last Position | [0] Rotor Detection | Start-up method for PM motors in VVC+, used when the motor may be free-running or stopped. |
| 1-71 | Start Delay | 0.0 - 10.0 s | 0 s | Delays the start of acceleration. The function used during the delay is chosen in 1-72. |
| 1-72 | Start Function | [0] DC Hold/delay time, [1] DC-Brake/delay time, [2] Coast/delay time, [3] Start speed cw, [4] Horizontal operation, [5] VVC+ clockwise | [2] Coast/delay time | Chooses what the drive does during the start delay: DC hold, DC brake, coast, or special start-speed functions for hoists and cone-rotor motors. |
| 1-75 | Start Speed [Hz] | 0 - 500.0 Hz | Size related | Frequency the output jumps to at start when a start-speed function is selected in 1-72. |
| 1-76 | Start Current | 0 - 1000 A | Size related | Extra current used at start with start-speed functions, for motors needing help to break away (e.g. cone rotor). |
| 1-80 | Function at Stop | [0] Coast, [1] DC hold / Motor Preheat, [3] Pre-magnetizing (options depend on motor construction) | [0] Coast | Chooses what the drive does after a stop command once speed has fallen to the level in 1-82. |
| 1-82 | Min Speed for Function at Stop [Hz] | 0 - 20 Hz | 0 Hz | Output frequency below which the function chosen in 1-80 becomes active. |
| 1-88 | AC Brake Gain | 1.0 - 2.0 | 1.4 | Strength of the AC brake. Higher values brake harder; 1.0 means no AC brake capability. |
| 1-90 | Motor Thermal Protection | [0] No protection, [1] Thermistor warning, [2] Thermistor trip, [3] ETR warning 1, [4] ETR trip 1, [22] ETR Trip - Extended Delay | [0] No protection | Selects how the motor is protected against overheating: using a PTC thermistor, or the drive's electronic thermal model. Leaving it at 0 gives no protection. |
| 1-93 | Thermistor Source | [0] None, [1] Analog Input 53, [2] Analog Input 54, [3] Digital input 18, [4] Digital input 19, [5] Digital input 32, [6] Digital input 33 | [0] None | Tells the drive which terminal the motor PTC thermistor is wired to. Set the matching input mode first (5-00, 6-19, 6-29). |
| 2-00 | DC Hold/Motor Preheat Current | 0 - 160 % | 50 % | Holding current for DC hold or motor preheating, as a percentage of rated motor current. |
| 2-01 | DC Brake Current | 0 - 150 % | 50 % | Braking current for DC brake, as a percentage of rated motor current. |
| 2-02 | DC Braking Time | 0 - 60 s | 10 s | How long DC brake current is applied after a stop. A value of 0 disables DC braking. |
| 2-04 | DC Brake Cut In Speed | 0 - 500 Hz | 0 Hz | Frequency at which DC braking is switched in during a stop. |
| 2-10 | Brake Function | [0] Off, [1] Resistor brake, [2] AC brake | [0] Off | Selects how regenerative energy is dealt with: no brake, a brake resistor, or AC braking. |
| 2-11 | Brake Resistor (ohm) | 0 - 6200 Ohm | Size related | Value of the connected brake resistor, used to monitor brake power. |
| 2-12 | Brake Power Limit (kW) | 0.001 - 2000 kW | Size related | Maximum power the brake resistor may dissipate, monitored over a 120 s window (see warning 26). |
| 2-16 | AC Brake, Max current | 0 - 160 % | 100 % | Current limit during AC braking. |
| 2-17 | Over-voltage Control | [0] Disabled, [1] Enabled (not at stop), [2] Enabled | [0] Disabled | Lets the drive stretch the deceleration ramp automatically to avoid DC-link overvoltage trips. |
| 2-19 | Over-voltage Gain | 0 - 200 % | 100 % | Tunes how strongly the over-voltage control reacts. |
| 2-20 | Release Brake Current | 0 - 100 A | 0 A | Motor current that must be reached before a mechanical brake is released. |
| 2-22 | Activate Brake Speed [Hz] | 0 - 400 Hz | 0 Hz | Frequency at which the mechanical brake is applied during stopping. |
| 2-23 | Activate Brake Delay | 0 - 5 s | 0 s | Delay before the mechanical brake is applied after stopping. |
| 3-00 | Reference Range | [0] Min - Max, [1] -Max - +Max | [0] Min - Max | Selects whether references may be only positive or both positive and negative. |
| 3-02 | Minimum Reference | -4999.000 - 4999.000 reference units | 0 | Lowest reference value obtainable from all sources; defines the minimum speed or process value. |
| 3-03 | Maximum Reference | -4999.0 - 4999 reference/feedback units | Size related | Highest reference value obtainable by summing all references. |
| 3-04 | Reference Function | [0] Sum, [1] External/Preset | [0] Sum | Either adds external and preset references together or switches between them with a command or digital input. |
| 3-10 | Preset Reference | -100 - 100 % (array of 8) | 0 % | Up to eight fixed references, selected by digital inputs or the bus, expressed as a percentage of the reference range. |
| 3-11 | Jog Speed [Hz] | 0 - 500.0 Hz | 5 Hz | Fixed output frequency used while jog is active. |
| 3-14 | Preset Relative Reference | -100 - 100 % | 0 % | Defines a percentage added to the actual reference to give a relative reference. |
| 3-15 | Reference 1 Source | [0] No function, [1] Analog Input 53, [2] Analog Input 54, [7] Frequency input 29, [8] Frequency input 33, [11] Local bus reference, [20] Digital pot.meter, [32] Bus PCD | [1] Analog Input 53 | Chooses the first source of the speed/process reference. |
| 3-16 | Reference 2 Source | Same options as 3-15 | [2] Analog Input 54 | Chooses the second reference source. |
| 3-17 | Reference 3 Source | Same options as 3-15 | [11] Local bus reference | Chooses the third reference source. |
| 3-41 | Ramp 1 Ramp Up Time | 0.01 - 3600 s | Size related | Acceleration time from 0 to the rated motor frequency (1-23). Too short a time can cause current limit or overcurrent. |
| 3-42 | Ramp 1 Ramp Down Time | 0.01 - 3600 s | Size related | Deceleration time from rated motor frequency to 0. Too short a time can cause DC overvoltage unless a brake is fitted. |
| 3-51 | Ramp 2 Ramp Up Time | 0.01 - 3600 s | Size related | Acceleration time for the second ramp, selectable by digital input. |
| 3-52 | Ramp 2 Ramp Down Time | 0.01 - 3600 s | Size related | Deceleration time for the second ramp. |
| 3-80 | Jog Ramp Time | 0.01 - 3600 s | Size related | Ramp time used when jogging. |
| 3-81 | Quick Stop Ramp Time | 0.01 - 3600 s | Size related | Deceleration time used for a quick stop command. |
| 4-10 | Motor Speed Direction | [0] Clockwise, [2] Both | [0] Clockwise | Allowed rotation directions. Must allow both directions if reversing is to be used. |
| 4-12 | Motor Speed Low Limit [Hz] | 0 - 400.0 Hz | 0 Hz | Minimum output frequency during operation. |
| 4-14 | Motor Speed High Limit [Hz] | 0.1 - 500 Hz | 65 Hz | Maximum output frequency the motor is allowed to run at; set it with the mechanical limits of the machine in mind. |
| 4-16 | Torque Limit Motor Mode | 0 - 1000 % | Size related | Torque limit when driving the load. Reaching it gives warning/alarm 12. |
| 4-17 | Torque Limit Generator Mode | 0 - 1000 % | 100 % | Torque limit when the load drives the motor (regenerating). |
| 4-18 | Current Limit | 0 - 1000 % | Size related | Output current limit. Reaching it gives warning/alarm 59. |
| 4-19 | Max Output Frequency | 0 - 500 Hz | Size related | Absolute upper limit on drive output frequency regardless of other settings; cannot exceed 10% of the switching frequency. |
| 4-20 | Torque Limit Factor Source | [0] No function, [2] Analog in 53, [4] Analog in 53 inv, [6] Analog in 54, [8] Analog in 54 inv, [18] Bus Control | [0] No function | Scales the torque limits with an analog input or the bus. |
| 4-22 | Break Away Boost | [0] Off, [1] On | [0] Off | Provides extra starting torque for loads that are hard to break away. |
| 4-30 | Motor Feedback Loss Function | [0] Disabled, [1] Warning, [2] Trip, [3] Jog, [4] Freeze Output, [5] Max Speed, [6] Switch to Open Loop | [2] Trip | What to do if the feedback signal is lost in closed-loop speed control. |
| 4-40 | Warning Freq. Low | 0 - 500 Hz | Size related | Frequency below which a low-frequency warning is issued. |
| 4-41 | Warning Freq. High | 0 - 500 Hz | Size related | Frequency above which a high-frequency warning is issued. |
| 4-50 | Warning Current Low | 0 - 500 A | 0 A | Motor current below which a low-current warning is issued; useful for detecting a lost load. |
| 4-51 | Warning Current High | 0.0 - 500.00 A | Size related | Motor current above which a high-current warning is issued. |
| 4-58 | Missing Motor Phase Function | [0] Off, [1] On | [1] On | Enables detection of a missing motor phase, giving alarms 30-32. |
| 4-61 | Bypass Speed From [Hz] | 0 - 500 Hz | 0 Hz | Start of a speed band the drive skips over to avoid mechanical resonance. |
| 4-63 | Bypass Speed To [Hz] | 0 - 500 Hz | 0 Hz | End of the skipped speed band. |
| 5-00 | Digital Input Mode | [0] PNP, [1] NPN | [0] PNP | Sets the wiring logic of the digital inputs (PNP active at 24 V, NPN active at 0 V). Wrong setting makes inputs seem dead. |
| 5-01 | Terminal 27 Mode | [0] Input, [1] Output | [0] Input | Selects whether terminal 27 acts as a digital input or output. |
| 5-10 | Terminal 18 Digital Input | Function list: [0] No operation, [1] Reset, [2] Coast inverse, [3] Coast and reset inverse, [4] Quick stop inverse, [5] DC-brake inverse, [6] Stop inverse, [8] Start, [9] Latched start, [10] Reversing, [11] Start reversing, [14] Jog, [15] Preset reference on, [16-18] Preset ref bit 0-2 and more | [8] Start | Assigns a function to terminal 18. The same function list applies to all digital inputs 5-10 to 5-15. |
| 5-11 | Terminal 19 Digital Input | Same function list as 5-10 | [10] Reversing | Assigns a function to terminal 19. |
| 5-12 | Terminal 27 Digital Input | Same function list as 5-10 | [2] Coast inverse | Assigns a function to terminal 27 (when set as input). Coast inverse by default means the terminal must be live for the drive to run, and AMA cannot run if it is off. |
| 5-13 | Terminal 29 Digital Input | Same function list as 5-10 plus [32] Pulse input | [14] Jog | Assigns a function to terminal 29. |
| 5-14 | Terminal 32 Digital Input | Same function list as 5-10 plus encoder input B | [0] No operation | Assigns a function to terminal 32. |
| 5-15 | Terminal 33 Digital Input | Same function list as 5-10 plus [32] Pulse input and encoder input A | [16] Preset ref bit 0 | Assigns a function to terminal 33. |
| 5-19 | Terminal 37/38 Safe Torque Off | [1] Safe Torque Off Alarm, [3] Safe Torque Off Warning | [1] Safe Torque Off Alarm | Sets how the drive reacts when STO is triggered: alarm 68 or warning 68, and whether restart is manual or automatic. |
| 5-30 | Terminal 27 Digital Output | Same function list as 5-40 (e.g. [1] Control ready, [2] Drive ready, [5] Running) | [0] No operation | Assigns a status function to terminal 27 when used as a digital output. |
| 5-40 | Function Relay | [0] No operation, [1] Control Ready, [2] Drive ready, [3] Drive rdy/remote, [4] Stand-by / no warning, [5] Running, [6] Running / no warning, and many further status functions | Size related | Selects which drive condition (ready, running, alarm, warning, etc.) switches the relay output. Array with one element per relay. |
| 5-41 | On Delay, Relay | 0 - 600 s | 0.01 s | Delay before the relay closes after its condition becomes true. |
| 5-42 | Off Delay, Relay | 0 - 600 s | 0.01 s | Delay before the relay opens after its condition becomes false. |
| 5-50 | Term. 29 Low Frequency | 0 - 31999 Hz | 4 Hz | Low end of the pulse frequency range on terminal 29, matched to the low reference/feedback value. |
| 5-51 | Term. 29 High Frequency | 1 - 32000 Hz | 32000 Hz | High end of the pulse frequency range on terminal 29. |
| 5-55 | Term. 33 Low Frequency | 0 - 31999 Hz | 4 Hz | Low end of the pulse frequency range on terminal 33. |
| 5-56 | Term. 33 High Frequency | 1 - 32000 Hz | 32000 Hz | High end of the pulse frequency range on terminal 33. |
| 6-00 | Live Zero Timeout Time | 1 - 99 s | 10 s | How long an analog signal must stay below its live-zero level before the reaction in 6-01 occurs. |
| 6-01 | Live Zero Timeout Function | [0] Off, [1] Freeze output, [2] Stop, [3] Jogging, [4] Max. speed, [5] Stop and trip | [0] Off | Reaction when an analog reference signal is lost (live zero error, warning/alarm 2). |
| 6-10 | Terminal 53 Low Voltage | 0 - 10 V | 0.07 V | Voltage on terminal 53 that corresponds to the low reference value. Also the basis for live-zero detection. |
| 6-11 | Terminal 53 High Voltage | 0 - 10 V | 10 V | Voltage on terminal 53 that corresponds to the high reference value. |
| 6-14 | Terminal 53 Low Ref./Feedb. Value | -4999 - 4999 | 0 | Reference or feedback value corresponding to the low voltage on terminal 53. |
| 6-15 | Terminal 53 High Ref./Feedb. Value | -4999 - 4999 | Size related | Reference or feedback value corresponding to the high voltage on terminal 53. |
| 6-16 | Terminal 53 Filter Time Constant | 0.01 - 10 s | 0.01 s | Low-pass filter on the terminal 53 signal to damp noise; longer means slower response. |
| 6-19 | Terminal 53 mode | [1] Voltage mode, [6] Digital input | [1] Voltage mode | Sets terminal 53 as an analog voltage input or as a digital input (e.g. for a thermistor). |
| 6-20 | Terminal 54 Low Voltage | 0 - 10 V | 0.07 V | Voltage on terminal 54 that corresponds to the low reference value. |
| 6-21 | Terminal 54 High Voltage | 0 - 10 V | 10 V | Voltage on terminal 54 that corresponds to the high reference value. |
| 6-22 | Terminal 54 Low Current | 0 - 20 mA | 4 mA | Current on terminal 54 that corresponds to the low reference value. A 4-20 mA loop below 2 mA triggers live zero. |
| 6-23 | Terminal 54 High Current | 0 - 20 mA | 20 mA | Current on terminal 54 that corresponds to the high reference value. |
| 6-24 | Terminal 54 Low Ref./Feedb. Value | -4999 - 4999 | 0 | Reference or feedback value corresponding to the low signal on terminal 54. |
| 6-25 | Terminal 54 High Ref./Feedb. Value | -4999 - 4999 | Size related | Reference or feedback value corresponding to the high signal on terminal 54. |
| 6-26 | Terminal 54 Filter Time Constant | 0.01 - 10 s | 0.01 s | Low-pass filter on the terminal 54 signal. |
| 6-29 | Terminal 54 mode | [0] Current mode, [1] Voltage mode | [1] Voltage mode | Sets terminal 54 for current or voltage input. It must match the actual signal and the hardware switch setting. |
| 6-90 | Terminal 42 Mode | [0] 0-20 mA, [1] 4-20 mA, [2] Digital Output | [0] 0-20 mA | Selects the signal type of terminal 42. |
| 6-91 | Terminal 42 Analog Output | [0] No operation, [100] Output frequency, [101] Reference, [102] Process Feedback, [103] Motor Current, [104] Torque rel to limit, [105] Torq relate to rated, [106] Power, [107] Speed, [111] Speed Feedback, [113] PID Clamped Output, [139] Bus Control, [143] Ext. CL, [254] DC Link Voltage | [0] No operation | Chooses which drive value is sent on the analog output terminal 42. |
| 7-00 | Speed PID Feedback Source | [1] 24V encoder, [6] Analog Input 53, [7] Analog Input 54, [8] Frequency input 29, [9] Frequency input 33, [20] None | [20] None | Selects the feedback device for closed-loop speed control. |
| 7-20 | Process CL Feedback 1 Resource | [0] No function, [1] Analog Input 53, [2] Analog Input 54, [3] Frequency input 29, [4] Frequency input 33 | [0] No function | Chooses the input that provides feedback for process closed loop control. |
| 7-30 | Process PID Normal/ Inverse Control | [0] Normal, [1] Inverse | [0] Normal | Normal raises output when feedback is below setpoint; inverse lowers output in that case (e.g. cooling). |
| 7-33 | Process PID Proportional Gain | 0 - 10 | 0.01 | Proportional gain of the process PID: how strongly the output reacts to the error. |
| 7-34 | Process PID Integral Time | 0.10 - 9999 s | 9999 s | Integral time of the process PID; shorter is faster correction but more risk of overshoot. 9999 effectively disables it. |
| 7-35 | Process PID Differentiation Time | 0 - 20 s | 0 s | Differentiation time of the process PID, rarely needed. |
| 8-01 | Control Site | [0] Digital and ctrl.word, [1] Digital only, [2] Controlword only | [0] Digital and ctrl.word | Chooses whether control comes from digital inputs, the fieldbus control word or both. Overrides the select parameters 8-50 to 8-58. |
| 8-02 | Control Source | [0] None, [1] FC Port, [2] FC USB, [3] Option A | Size related | Selects the interface the control word and bus reference are accepted from. |
| 8-03 | Control Timeout Time | 0.5 - 6000 s | 1 s | Maximum time allowed between control messages; if exceeded the function in 8-04 is executed. |
| 8-04 | Control Timeout Function | [0] Off, [1] Freeze output, [2] Stop, [3] Jogging, [4] Max. speed, [5] Stop and trip | [0] Off | Reaction when serial communication times out (warning/alarm 17). |
| 8-10 | Control Word Profile | [0] FC profile, [1] PROFIdrive profile, [5] ODVA, [7] CANopen DSP 402 | [0] FC profile | Selects the control and status word profile used by the fieldbus. |
| 8-30 | Protocol | [0] FC, [2] Modbus RTU | [0] FC | Selects the protocol on the RS485 port. Choose Modbus RTU for Modbus masters. |
| 8-31 | Address | 0 - 247 | 1 | Station address of the drive on the serial bus. |
| 8-32 | Baud Rate | [0] 2400, [1] 4800, [2] 9600, [3] 19200, [4] 38400, [5] 57600, [6] 76800, [7] 115200 Baud | Size related | Serial communication speed; must match the master. |
| 8-33 | Parity / Stop Bits | [0] Even, 1 stop bit, [1] Odd, 1 stop bit, [2] No parity, 1 stop bit, [3] No parity, 2 stop bits | Size related | Parity and stop bit format of the serial port; must match the master. |
| 8-35 | Minimum Response Delay | 0.0010 - 0.5 s | 0.01 s | Minimum pause before the drive answers a serial request, for slow masters. |
| 8-36 | Maximum Response Delay | 0.1 - 10.0 s | Size related | Maximum time the drive may take to answer a request. |
| 8-50 | Coasting Select | [0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR | [3] Logic OR | Chooses whether coast is triggered by a digital input, the bus, or a combination. The other 8-5* parameters work in the same way. |
| 8-51 | Quick Stop Select | [0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR | [3] Logic OR | Selects the source of the quick stop command. |
| 8-53 | Start Select | [0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR | [3] Logic OR | Selects the source of the start command. |
| 8-54 | Reversing Select | [0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR | [3] Logic OR | Selects the source of the reverse command. |
| 8-56 | Preset Reference Select | [0] Digital input, [1] Bus, [2] Logic AND, [3] Logic OR | [3] Logic OR | Selects the source of the preset reference selection. |
| 8-80 | Bus Message Count | 0 - 4294967295 | 0 | Counter of valid messages seen on the bus; read-only diagnostic. |
| 8-81 | Bus Error Count | 0 - 4294967295 | 0 | Counter of messages with errors; useful to detect noise or wrong settings. |
| 8-82 | Slave Messages Rcvd | 0 - 4294967295 | 0 | Number of valid messages addressed to this drive. |
| 8-83 | Slave Error Count | 0 - 4294967295 | 0 | Number of messages the drive could not execute. |
| 8-85 | Slave Timeout Errors | 0 - 4294967295 | 0 | Number of times a slave message timed out. |
| 8-88 | Reset FC port Diagnostics | [0] Do not reset, [1] Reset counter | [0] Do not reset | Clears the bus diagnostic counters in 8-80 to 8-85. |
| 14-01 | Switching Frequency | [0] Ran3, [1] Ran5, [2] 2.0 kHz, [3] 3.0, [4] 4.0, [5] 5.0, [6] 6.0, [7] 8.0, [8] 10.0, [9] 12.0, [10] 16.0 kHz | Size related | Inverter carrier frequency. Higher values mean quieter motor but more drive heating and derating; lower values mean less heat. |
| 14-03 | Overmodulation | [0] Off, [1] On | [1] On | Allows the output voltage to rise above normal for more motor voltage at high speed, at the cost of torque ripple. |
| 14-10 | Mains Failure | [0] No function, [1] Ctrl. ramp-down, [2] Ctrl. ramp-down and trip, [3] Coasting, [4]-[7] kinetic back-up and alarm variants | [0] No function | Defines how the drive reacts to a short supply dip once the voltage falls to the level in 14-11: ignore it, ramp down under control, coast, or use kinetic back-up. Cannot be changed while the motor runs. |
| 14-11 | Mains Fault Voltage Level | 100 - 800 V | Size related | Supply voltage threshold at which the mains failure function in 14-10 starts (alarm/warning 36). |
| 14-12 | Function at Mains Imbalance | [0] Trip, [1] Warning, [2] Disabled | [0] Trip | Reaction to severe supply voltage imbalance or phase loss. |
| 14-20 | Reset Mode | [0] Manual reset, [1]-[10] Automatic reset x1...x10, [11] x15, [12] x20, [13] Infinite auto reset, [14] Reset at power-up | [0] Manual reset | Chooses whether trips are reset manually or automatically after a trip. Automatic reset can restart the motor without warning, so use with care. Does not apply to alarms 68 and 188. |
| 14-21 | Automatic Restart Time | 0 - 600 s | 10 s | Delay between a trip and the automatic reset attempt. |
| 14-22 | Operation Mode | [0] Normal operation, [2] Initialisation | [0] Normal operation | Set to Initialisation to restore factory defaults; the reset takes effect at the next power-up. |
| 14-24 | Trip Delay at Current Limit | 0 - 60 s | 60 s | Time the drive can run at current limit before tripping. 60 means no trip. |
| 14-25 | Trip Delay at Torque Limit | 0 - 60 s | 60 s | Time the drive can run at torque limit before tripping. 60 means no trip. |
| 14-27 | Action At Inverter Fault | [0] Trip, [1] Warning | [1] Warning | Chooses how the drive reacts to overvoltage or ground-fault conditions: Trip disables the protection filters and trips at the first fault, Warning keeps the protection filters running. |
| 14-28 | Production Settings | [0] No action, [1] Service reset, [3] Software Reset | [0] No action | Service-oriented function for resets; leave at no action in normal use. |
| 14-29 | Service Code | 0 - 0x7FFFFFFF | 0 | Only for use by service technicians. |
| 14-40 | VT Level | 40 - 90 % | 66 % | Magnetisation level used in variable torque operation (see 1-03). |
| 14-52 | Fan Control | [5] Constant-on mode, [6] Constant-off mode, [7] On-when-Inverter-is-on, [8] Variable-speed mode | [8] Variable-speed mode | Selects how the internal cooling fan is controlled. |
| 14-55 | Output Filter | [0] No Filter, [1] Sine-Wave Filter | [0] No Filter | Tells the drive that a sine-wave filter is fitted on the output so it can adjust its operation accordingly. |
| 14-61 | Function at Inverter Overload | [0] Trip, [1] Derate | [0] Trip | Chooses whether inverter overload trips the drive or reduces output (derating). |
| 14-90 | Fault Level | Per alarm: [0] Off, [3] Trip Lock, [4] Trip w. delayed reset, [5] Flystart | [3] Trip Lock | Lets you change the severity of selected alarms (such as ground fault or overcurrent) to trip lock, delayed-reset trip or similar. |
| 15-00 | Operating hours | 0 - 0x7fffffff h | 0 h | Total hours the drive has been powered up. |
| 15-01 | Running Hours | 0 - 0x7fffffff h | 0 h | Total hours the motor has been running. |
| 15-02 | kWh Counter | 0 - 2147483647 kWh | 0 kWh | Accumulated energy consumption of the motor. |
| 15-03 | Power Up's | 0 - 2147483647 | 0 | Number of times the drive has been powered up. |
| 15-04 | Over Temp's | 0 - 65535 | 0 | Number of times the drive has had an over-temperature fault. |
| 15-05 | Over Volt's | 0 - 65535 | 0 | Number of times the drive has had a DC overvoltage fault. |
| 15-06 | Reset kWh Counter | [0] Do not reset, [1] Reset counter | [0] Do not reset | Resets the kWh counter (15-02). |
| 15-07 | Reset Running Hours Counter | [0] Do not reset, [1] Reset counter | [0] Do not reset | Resets the running hours counter (15-01). |
| 15-30 | Alarm Log: Error Code | 0 - 255 (array) | 0 | History of recent alarm codes; the newest entries are first. Use it to see what tripped the drive. |
| 15-31 | InternalFaultReason | -32767 - 32767 | 0 | Extra code describing an internal fault; give it to the supplier when reporting alarm 38. |
| 15-40 | FC Type | text | 0 | Drive type designation. |
| 15-41 | Power Section | text | 0 | Power section designation of the drive. |
| 15-42 | Voltage | text | 0 | Voltage class of the power section. |
| 15-43 | Software Version | text | 0 | Installed software version. |
| 15-46 | Drive Ordering No | text | 0 | Ordering number of the drive. |
| 15-51 | Frequency Converter Serial Number | text | 0 | Serial number of the drive. |
| 16-00 | Control Word | 0 - 65535 | 0 | Control word last received from the bus or terminals, shown in hex. |
| 16-01 | Reference [Unit] | -4999 - 4999 reference/feedback units | 0 | Present reference in the selected reference unit. |
| 16-03 | Status Word | 0 - 65535 | 0 | Current drive status word, in hex. |
| 16-05 | Main Actual Value [%] | -200 - 200 % | 0 % | The main actual value word sent with the status word, as a percentage. |
| 16-10 | Power [kW] | 0 - 1000 kW | 0 kW | Present motor power in kW. |
| 16-12 | Motor Voltage | 0 - 65535 V | 0 V | Voltage supplied to the motor. |
| 16-13 | Frequency | 0 - 6553.5 Hz | 0 Hz | Present output frequency (without resonance dampening). |
| 16-14 | Motor current | 0 - 655.35 A | 0 A | Present motor current. |
| 16-15 | Frequency [%] | 0 - 6553.5 % | 0 % | Output frequency as a percentage of the maximum frequency. |
| 16-17 | Speed [RPM] | -30000 - 30000 RPM | 0 RPM | Actual motor speed. |
| 16-18 | Motor Thermal | 0 - 100 % | 0 % | Calculated thermal load of the motor; around 100% triggers the ETR protection. |
| 16-22 | Torque [%] | -200 - 200 % | 0 % | Present torque as a percentage of the rated motor torque. |
| 16-30 | DC Link Voltage | 0 - 65535 V | 0 V | Present DC-link voltage; useful when diagnosing alarms 7 and 8. |
| 16-33 | Brake Energy Average | 0 - 10000 kW | 0 kW | Average power sent to the brake resistor. |
| 16-34 | Heatsink Temp. | -128 - 127 deg C | 0 deg C | Present heatsink temperature. |
| 16-35 | Inverter Thermal | 0 - 255 % | 0 % | Calculated thermal load of the inverter. |
| 16-36 | Inv. Nom. Current | 0 - 655.35 A | read-only | Nominal current of the inverter. |
| 16-37 | Inv. Max. Current | 0 - 655.35 A | read-only | Maximum current of the inverter. |
| 16-39 | Control Card Temp. | 0 - 65535 deg C | 0 deg C | Present control card temperature. |
| 16-52 | Feedback[Unit] | -4999 - 4999 process units | 0 | Feedback value in the selected process unit. |
| 16-60 | Digital Input | 0 - 4095 | 0 | Binary state of the digital inputs, useful for checking wiring. |
| 16-61 | Terminal 53 Setting | [1] Voltage mode, [6] Digital input | Size related | Shows whether terminal 53 is set to voltage or digital input. |
| 16-62 | Analog input 53 | 0 - 20 | 1 | Present value on analog input 53. |
| 16-63 | Terminal 54 Setting | [0] Current mode, [1] Voltage mode | Size related | Shows whether terminal 54 is set to current or voltage. |
| 16-64 | Analog input 54 | 0 - 20 | 1 | Present value on analog input 54. |
| 16-65 | Analog output 42 [mA] | 0 - 20 mA | 0 mA | Present current on analog output 42. |
| 16-66 | Digital Output | 0 - 63 | 0 | Binary state of the digital outputs. |
| 16-71 | Relay output | 0 - 31 | 0 | Binary state of the relay outputs. |
| 16-82 | Fieldbus REF 1 | -32768 - 32767 | 0 | Reference word last received from the fieldbus, for checking communication. |
| 16-90 | Alarm Word | 0 - 0xFFFFFFFF | 0 | Alarm word in hex; bits map to active alarms (see Table 6.3). |
| 16-91 | Alarm Word 2 | 0 - 0xFFFFFFFF | 0 | Second alarm word in hex. |
| 16-92 | Warning Word | 0 - 0xFFFFFFFF | 0 | Warning word in hex; bits map to active warnings. |
| 16-93 | Warning Word 2 | 0 - 0xFFFFFFFF | 0 | Second warning word in hex. |
| 16-94 | Ext. Status Word | 0 - 0xFFFFFFFF | 0 | Extended status word with running states such as ramping, braking, sleep. |
| 16-95 | Ext. Status Word 2 | 0 - 0xFFFFFFFF | 0 | Second extended status word. |
| 16-97 | Alarm Word 3 | 0 - 0xFFFFFFFF | 0 | Third alarm word in hex. |
| 16-98 | Warning Word 3 | 0 - 4294967295 | 0 | Third warning word in hex. |
| 22-40 | Minimum Run Time | 0 - 600 s | 10 s | Minimum time the motor runs after a start in sleep mode, to avoid short cycling. |
| 22-41 | Minimum Sleep Time | 0 - 600 s | 10 s | Minimum time the drive stays in sleep before waking. |
| 22-43 | Wake-Up Speed [Hz] | 0 - 400.0 Hz | 10 | Speed above which the drive wakes from sleep when in open loop. |
| 22-44 | Wake-Up Ref./FB Diff | 0 - 100 % | 10 % | Difference between reference and feedback that wakes the drive from sleep in closed loop. |
| 22-60 | Broken Belt Function | [0] Off, [1] Warning, [2] Trip | [0] Off | Reaction when load torque falls below the broken belt torque (22-61) for the delay in 22-62. |
| 22-61 | Broken Belt Torque | 5 - 100 % | 10 % | Torque level below which a broken belt is assumed. |
| 22-62 | Broken Belt Delay | 0 - 600 s | 10 s | Time torque must stay low before the broken belt reaction occurs. |
| 30-22 | Locked Rotor Protection | [0] Off, [1] On | [0] Off | Enables locked-rotor detection (alarm 99). |
| 30-23 | Locked Rotor Detection Time [s] | 0.05 - 1 s | 0.10 s | Time the locked condition must persist before alarm 99 is raised. |
See also the Danfoss VLT FC 280 fault codes. ServMod reads, compares and backs up these parameters from your phone: how to connect.
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.