Fault codes / Danfoss VLT FC 280
Danfoss VLT FC 280 fault codes: meaning and checks
56 fault and warning codes of the Danfoss VLT FC 280, each with what it means and what to check first. Tap a code for the full checklist.
| Code | Name | Meaning |
|---|---|---|
| W2/A2 | Live zero error | The signal on analog input 53 or 54 has fallen below 50% of the low end configured for that input (par. 6-10... |
| W3 | No motor | No motor is detected on the drive output. |
| W4/A4 | Mains phase loss | A supply phase is missing or the supply voltage imbalance is too high. Mains distortion can also cause it. |
| W7/A7 | DC overvoltage | The DC-link voltage has exceeded its limit. Mains distortion can also cause it. |
| W8/A8 | DC undervoltage | The DC-link voltage has dropped below the low-voltage warning limit. Mains distortion can also cause it. |
| W9/A9 | Inverter overloaded | The drive has been carrying more than 100% load for too long. |
| W10/A10 | Motor ETR overtemperature | The electronic thermal model says the motor is too hot after running above 100% load too long. |
| W11/A11 | Motor thermistor overtemperature | The thermistor or its wiring is disconnected, or the motor is overheated. |
| W12/A12 | Torque limit | Torque has exceeded the motor-mode limit (4-16) or generator-mode limit (4-17). |
| W13/A13 | Overcurrent | The inverter peak current limit was exceeded. If it appears at power-up, power cables may be wired to the... |
| A14 | Ground fault | Current is leaking from the output phases to ground. |
| A16 | Short circuit | There is a short circuit in the motor or at the motor terminals. |
| W17/A17 | Control word timeout | The drive is no longer receiving communication from the master. |
| A25 | Brake resistor short-circuited | The brake resistor is shorted, so the brake function has been disabled. |
| W26/A26 | Brake overload | Power sent to the brake resistor over the last 120 s exceeded the allowed limit. |
| A27 | Brake IGBT/chopper short-circuited | The brake transistor is shorted, so the brake function has been disabled. |
| A28 | Brake check | The brake resistor is not connected or not working. |
| A30 | Motor phase U missing | Motor output phase U is not present. |
| A31 | Motor phase V missing | Motor output phase V is not present. |
| A32 | Motor phase W missing | Motor output phase W is not present. |
| W34/A34 | Fieldbus fault | PROFIBUS communication problems have occurred. |
| A35 | Option fault | The fieldbus option reports internal faults. |
| W36/A36 | Mains failure | Active only when the supply voltage is below the level in 14-11 and 14-10 is not set to No function. |
| A38 | Internal fault | An internal drive fault has occurred. |
| W40 | Overload on terminal 27 | The digital output on terminal 27 is overloaded. |
| A46 | Gate drive voltage fault | A fault in the gate-drive supply of the power card has been detected. |
| W47/A47 | 24 V supply low | The 24 V DC supply may be overloaded. |
| A49 | Speed limit | Motor speed is below the trip speed low limit set in 1-87. |
| A50 | AMA calibration failed | A calibration error occurred during the automatic motor adaptation. |
| A51 | AMA check Unom and Inom | The motor voltage and/or motor current settings are wrong. |
| A52 | AMA low Inom | The motor current is too low for AMA. |
| A53 | AMA big motor | The motor is too large for AMA to run. |
| A54 | AMA small motor | The motor is too small for AMA to run. |
| A55 | AMA parameter range | Motor parameter values are outside the acceptable range, so AMA does not run. |
| A56 | AMA interrupt | The AMA was interrupted. |
| A57 | AMA timeout | The AMA timed out. |
| A58 | AMA internal | An internal fault occurred during AMA. |
| W59/A59 | Current limit | The drive is overloaded and has reached its current limit. |
| W60/A60 | External interlock | The external interlock input has been activated. |
| A61 | Encoder loss | The encoder or feedback signal was lost. |
| A63 | Mechanical brake low | The motor current did not reach the brake release current within the start delay. |
| W65/A65 | Control card temperature | The control card cut-out temperature has exceeded its upper limit. |
| A67 | Option change | A new option has been detected or a fitted one removed. |
| W68/A68 | Safe Torque Off | STO has been activated. In manual restart mode, restore 24 V DC to terminals 37 and 38 and give a reset; in... |
| W69/A69 | Power card temperature | The power card cut-out temperature has exceeded its upper limit. |
| A80 | Drive initialized to default | All parameters have been set back to factory defaults. |
| W87 | Auto DC braking | Occurs on IT mains when the drive coasts and the DC link exceeds 830 V (400 V units) or 425 V (200 V units)... |
| A88 | Option detection | The option has been removed successfully. |
| W95/A95 | Broken belt | A broken belt or coupling is suspected. |
| A99 | Locked rotor | The rotor is blocked. |
| A120 | Position control fault | A fault occurred in position control. |
| A126 | Motor rotating | A PM motor is rotating while AMA is being performed. |
| W127 | Back EMF too high | The back EMF of the PM motor is too high before starting. |
| A188 | STO internal fault | 24 V DC is applied to only one of the two STO terminals (37 and 38), or a fault was detected in the STO... |
| nw run | Not while running | Display message: the parameter can only be changed when the motor is stopped. |
| Err. | Wrong password entered | Display message shown when a wrong password is used to change a password-protected parameter. |
Source: VLT Midi Drive FC 280 Programming Guide (MG07C402, 02/2019). Manufacturer page. See also the Danfoss VLT FC 280 parameter list, the connection and backup page and the wiring diagrams.
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.