The inverter peak current limit was exceeded. If it appears at power-up, power cables may be wired to the motor terminals by mistake.

What to check

  1. Check that the supply cables are not connected to the motor terminals
  2. Check motor and cable insulation and that the motor data matches the nameplate (1-2*)
  3. Lengthen the acceleration ramp or reduce the load
  4. Check for a locked or jammed mechanism

Source: VLT Midi Drive FC 280 Programming Guide (MG07C402, 02/2019), page 141 (warning/alarm/trip-lock). Manufacturer page.

Keep the settings safe before you change anything

Before you reset, replace or reprogram a Danfoss VLT FC 280, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Danfoss VLT FC 280 to a phone and the wiring diagrams.

Download free for Android

Other Danfoss VLT FC 280 fault codes

W2/A2W3W4/A4W7/A7W8/A8W9/A9W10/A10W11/A11W12/A12W13/A13A14A16W17/A17A25W26/A26A27A28A30A31A32W34/A34A35W36/A36A38W40A46W47/A47A49A50A51A52A53A54A55A56A57A58W59/A59W60/A60A61A63W65/A65A67W68/A68W69/A69A80W87A88W95/A95A99A120A126W127A188nw runErr.

This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.