Fault codes / Danfoss VLT FC 280 / W9/A9
Danfoss VLT FC 280 fault W9/A9: Inverter overloaded
The drive has been carrying more than 100% load for too long.
What to check
- Compare motor current (16-14) and inverter thermal (16-35) with the rating
- Reduce the load or use a larger drive
- Check ramp times and the switching frequency setting (14-01)
Source: VLT Midi Drive FC 280 Programming Guide (MG07C402, 02/2019), page 141 (warning/alarm). Manufacturer page.
Keep the settings safe before you change anything
Before you reset, replace or reprogram a Danfoss VLT FC 280, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Danfoss VLT FC 280 to a phone and the wiring diagrams.
Other Danfoss VLT FC 280 fault codes
W2/A2W3W4/A4W7/A7W8/A8W9/A9W10/A10W11/A11W12/A12W13/A13A14A16W17/A17A25W26/A26A27A28A30A31A32W34/A34A35W36/A36A38W40A46W47/A47A49A50A51A52A53A54A55A56A57A58W59/A59W60/A60A61A63W65/A65A67W68/A68W69/A69A80W87A88W95/A95A99A120A126W127A188nw runErr.
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.