Fault codes / Danfoss VLT FC 280 / W2/A2
Danfoss VLT FC 280 fault W2/A2: Live zero error
The signal on analog input 53 or 54 has fallen below 50% of the low end configured for that input (par. 6-10, 6-20 or 6-22).
What to check
- Check wiring and connectors on terminals 53/54 and the signal source
- Compare the live signal with the low-voltage/low-current scaling in 6-10, 6-20, 6-22
- Review live-zero timeout settings 6-00 and 6-01
Source: VLT Midi Drive FC 280 Programming Guide (MG07C402, 02/2019), page 141 (warning/alarm). Manufacturer page.
Keep the settings safe before you change anything
Before you reset, replace or reprogram a Danfoss VLT FC 280, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Danfoss VLT FC 280 to a phone and the wiring diagrams.
Other Danfoss VLT FC 280 fault codes
W2/A2W3W4/A4W7/A7W8/A8W9/A9W10/A10W11/A11W12/A12W13/A13A14A16W17/A17A25W26/A26A27A28A30A31A32W34/A34A35W36/A36A38W40A46W47/A47A49A50A51A52A53A54A55A56A57A58W59/A59W60/A60A61A63W65/A65A67W68/A68W69/A69A80W87A88W95/A95A99A120A126W127A188nw runErr.
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.