Fault codes / Omron MX2 parameters
Omron MX2 parameter list
246 parameters of the Omron MX2 with range, default value and a short description. Source: 3G3MX2-V2 User's Manual (I666-E1-03, August 2024).
| No. | Name | Range | Default | What it does |
|---|---|---|---|---|
| d001 | Output frequency monitor | 0.00-590.00 Hz (0.0-590.0 in HF mode) | - | Live output frequency; also the default screen after power-up. |
| d002 | Output current monitor | 0.00-655.35 A | - | Shows motor current as filtered by the inverter - first thing to check for load problems. |
| d003 | Run direction monitor | F / o / r | - | Shows whether the inverter is running forward, stopped or reverse. |
| d005 | Multi-function input monitor | S1-S7, RP status | - | Shows which control inputs the inverter sees as ON; use it to check wiring. |
| d006 | Multi-function output monitor | P1, P2, MA status | - | Shows the state of the open-collector outputs and relay. |
| d008 | Real frequency monitor | -590.00 to 590.00 Hz | - | Actual speed measured by the encoder when feedback is used. |
| d013 | Output voltage monitor | 0.0-600.0 V | - | Voltage the inverter is putting out to the motor. |
| d014 | Input power monitor | 0.0-100.0 kW | - | Electrical power drawn by the drive. |
| d016 | Total RUN time monitor | 0-1000000 h | - | Cumulative hours the drive has been running. |
| d017 | Total power ON time monitor | 0-1000000 h | - | Cumulative hours the drive has been powered. |
| d018 | Fin temperature monitor | 20.0-150.0 degC | - | Heat sink temperature - useful when investigating E21. |
| d022 | Life assessment monitor | 1: capacitor, 2: fan | - | Indicates whether the main capacitors or cooling fan have reached the end of expected life. |
| d060 | Inverter mode monitor | I-C / I-V / H-I / P | - | Shows the active mode: induction normal load, induction light load, high-frequency or PM motor. |
| d062 | Frequency reference source monitor | 00-27 (source code) | - | Tells you where the current frequency command is coming from. |
| d063 | RUN command source monitor | 1 terminal, 2 operator, 3 Modbus, 4 option | - | Tells you which source is issuing the RUN command. |
| d080 | Fault counter | 0-65535 times | - | How many trips have occurred. |
| d081 | Fault monitor 1 (latest) to 6 (d081-d086) | Fault code plus snapshot | - | Trip history with output frequency, current, DC bus voltage and run/power-on hours at the moment of the fault. |
| d090 | Warning monitor | Warning code | - | Latest parameter-conflict warning. |
| d102 | DC voltage monitor | 0.0-1000.0 V | - | DC bus voltage - helps diagnose E07/E09. |
| d103 | Regenerative braking load rate monitor | 0.0-100.0 % | - | How hard the braking chopper is working. |
| d104 | Electronic thermal load rate monitor | 0.0-100.0 % | - | Percentage of the thermal overload budget used; near 100 means E05 is imminent. |
| F001 | Output frequency setting/monitor | 0.0, starting freq to max freq (Hz) | 6.00 | Frequency reference entered from the keypad; also shows the set speed. |
| F002 | 1st acceleration time 1 | 0.00-3600.00 s | 10.00 (30.00 in HF mode) | Time to ramp up from zero to maximum frequency. |
| F202 | 2nd acceleration time 1 | 0.00-3600.00 s | 10.00 (30.00 in HF mode) | Ramp-up time used when the second motor/setting set is selected. |
| F003 | 1st deceleration time 1 | 0.00-3600.00 s | 10.00 (30.00 in HF mode) | Time to ramp down from maximum frequency to zero; too short can cause E07. |
| F203 | 2nd deceleration time 1 | 0.00-3600.00 s | 10.00 (30.00 in HF mode) | Ramp-down time for the second setting set. |
| F004 | RUN direction selection | 00 forward / 01 reverse | 00 | Direction used when running from the keypad. |
| A001 | 1st frequency reference selection | 00 operator volume, 01 terminal, 02 operator F001, 03 Modbus, 04 option, 06 pulse train, 07 DriveProgramming, 10 operation function | 02 | Chooses where the speed command comes from. If the motor runs at 0 Hz, check this first. |
| A201 | 2nd frequency reference selection | as A001 | 02 | Speed command source for the second setting set. |
| A002 | 1st RUN command selection | 01 terminal, 02 operator, 03 Modbus, 04 option | 02 | Chooses where the start/stop command comes from. |
| A202 | 2nd RUN command selection | as A002 | 02 | Start/stop source for the second setting set. |
| A003 | 1st base frequency | 30.0 to A004 (Hz) | 60.0 (580.0 in HF mode) | Frequency at which full motor voltage is reached; set to the motor nameplate frequency. |
| A203 | 2nd base frequency | 30.0 to A204 (Hz) | 60.0 (580.0 in HF mode) | Base frequency for the second motor. |
| A004 | 1st maximum frequency | A003 to 590.0 (Hz) | 60.0 (580.0 in HF mode) | Highest output frequency allowed. |
| A204 | 2nd maximum frequency | A203 to 590.0 (Hz) | 60.0 (580.0 in HF mode) | Highest output frequency for the second set. |
| A005 | FV/FI selection | 00 FV/FI, 02 FV/volume, 03 FI/volume | 00 | Selects which analog inputs are switched by the AT terminal. |
| A011 | FV start frequency | 0.00-590.00 Hz | 0.00 | Frequency corresponding to the start of the analog voltage range. |
| A012 | FV end frequency | 0.00-590.00 Hz | 0.00 | Frequency corresponding to the end of the analog voltage range. |
| A013 | FV start ratio | 0 to A014 % | 0. | Input percentage where the FV start frequency applies. |
| A014 | FV end ratio | A013 to 100 % | 100. | Input percentage where the FV end frequency applies. |
| A015 | FV start selection | 00 use A011, 01 0 Hz | 01 | Whether the output at the start of the range is A011 or zero. |
| A016 | Analog input filter | 1-30, 31 (500 ms with hysteresis) | 8. | Smooths noisy analog speed signals at the cost of response. |
| A019 | Multi-step speed selection | 00 binary (4 terminals), 01 bit (7 terminals) | 00 | Chooses binary or bit-type selection of preset speeds. |
| A020 | 1st multi-step speed reference 0 | Start freq to max freq (Hz) | 6.00 | Preset speed 0, which is also the keypad frequency. |
| A021 | Multi-step speed reference 1 (A021-A035: 1 to 15) | Start freq to max freq (Hz) | 0.00 | Preset speeds 1-15 selected by CF1-CF4 or SF inputs. |
| A038 | Jogging frequency | Start freq to 10.00 Hz (100.00 in HF mode) | 6.00 | Speed used for jog operation. |
| A039 | Jogging stop selection | 00-05 | 04 | How the motor stops after a jog: free-run, decel or DC brake, and whether jog is allowed while running. |
| A041 | 1st torque boost selection | 00 manual / 01 automatic | 01 | Selects manual or automatic low-speed torque boost. |
| A042 | 1st manual torque boost voltage | 0.0-20.0 % | 1.0 | Extra voltage at low frequency; raise carefully to improve starting torque. |
| A043 | 1st manual torque boost frequency | 0.0-50.0 % of base freq | 5.0 | Frequency up to which the manual boost is applied. |
| A044 | 1st control method | 00 constant torque VC, 01 reduced torque VP, 02 free V/f, 03 sensorless vector | 00 | Selects the V/f pattern or sensorless vector control. |
| A244 | 2nd control method | as A044 | 00 | Control method for the second setting set. |
| A045 | 1st output voltage gain | 20-100 % | 100. | Scales the output voltage; reducing it can quiet an overexcited motor. |
| A046 | 1st automatic torque boost voltage compensation gain | 0-255 | 100. | Tuning of the automatic boost voltage. |
| A047 | 1st automatic torque boost slip compensation gain | 0-255 | 0. | Tuning of the automatic boost slip compensation. |
| A051 | DC injection braking selection | 00 off, 01 on, 02 at set freq only | 00 | Enables DC injection braking at stop. |
| A052 | DC injection braking frequency | 0.00-60.00 Hz | 0.50 | Frequency below which DC braking starts during deceleration. |
| A053 | DC injection braking delay time | 0.0-5.0 s | 0.0 | Wait before DC braking begins. |
| A054 | DC injection braking power | 0-100 / 70 % (normal/light load) | 50. | Strength of the braking current. |
| A055 | DC injection braking time | 0.0-60.0 s | 0.5 | How long DC braking lasts. |
| A057 | Startup DC injection braking power | 0-100 / 70 % (normal/light load) | 0. | DC braking applied before starting, e.g. to stop a spinning load. |
| A058 | Startup DC injection braking time | 0.0-60.0 s | 0.0 | Duration of start-up DC braking. |
| A061 | 1st frequency upper limit | 0.00 (off) or limit lower to A004 (Hz) | 0.00 | Upper clamp on the frequency reference. |
| A062 | 1st frequency lower limit | 0.00 (off) or start freq to upper limit (Hz) | 0.00 | Minimum run frequency once running. |
| A063 | Jump frequency 1 | 0.00-590.00 Hz | 0.00 | Centre of a speed band to skip, used to avoid mechanical resonance. |
| A064 | Jump frequency width 1 | 0.00-10.00 Hz (100.00 in HF mode) | 0.50 | Width of the skipped band around jump 1. |
| A071 | PID selection | 00 off, 01 on, 02 on with reverse output | 00 | Enables the built-in PID loop. |
| A072 | PID P gain | 0.00-25.00 | 1.00 | Proportional gain of the PID loop. |
| A073 | PID I gain | 0.0-3600.0 s | 1.0 | Integral time of the PID loop. |
| A074 | PID D gain | 0.00-100.00 s | 0.00 | Derivative time of the PID loop. |
| A075 | PID scale | 0.01-99.99 | 1.00 | Scaling factor for PID values on the display. |
| A076 | PID feedback selection | 00 FI, 01 FV, 02 Modbus, 03 pulse train, 10 operation function | 00 | Which input carries the PID feedback. |
| A081 | 1st AVR selection | 00 always on, 01 always off, 02 off during decel | 02 | Automatic voltage regulation mode, compensating supply voltage variation. |
| A082 | 1st motor rated voltage selection | 200 V class: 200/215/220/230/240; 400 V class: 380/400/415/440/460/480 | 200 / 400 | Set to the motor's rated voltage. |
| A085 | Operation mode selection | 00 normal, 01 energy saving | 00 | Enables energy-saving operation. |
| A092 | 1st acceleration time 2 | 0.00-3600.00 s | 10.00 (15.00 in HF mode) | Second ramp-up time used with 2CH or frequency switching. |
| A093 | 1st deceleration time 2 | 0.00-3600.00 s | 10.00 (15.00 in HF mode) | Second ramp-down time. |
| A094 | 1st 2-step accel/decel selection | 00 2CH terminal, 01 by frequency, 02 only at fwd/rev switching | 00 | How the second ramp times are selected. |
| A097 | Acceleration pattern selection | 00 line, 01 S-curve, 02 U-curve, 03 inverted U, 04 EL-S | 01 | Shape of the acceleration ramp. |
| A098 | Deceleration pattern selection | 00 line, 01 S-curve, 02 U-curve, 03 inverted U, 04 EL-S | 01 | Shape of the deceleration ramp. |
| A101 | FI start frequency | 0.00-590.00 Hz | 0.00 | Frequency at the start of the FI current input range. |
| A102 | FI end frequency | 0.00-590.00 Hz | 0.00 | Frequency at the end of the FI current input range. |
| A103 | FI start ratio | 0 to A104 % | 20. | Percent of input (4 mA is 20%) where the start frequency applies. |
| A104 | FI end ratio | A103 to 100 % | 100. | Percent of input where the end frequency applies. |
| A105 | FI start selection | 00 use A101, 01 0 Hz | 00 | Output below the FI start point. |
| A131 | Acceleration curve parameter | 1-10 | 2 | Curvature of the S-type acceleration. |
| A132 | Deceleration curve parameter | 1-10 | 2 | Curvature of the S-type deceleration. |
| A145 | Frequency addition amount | 0.00-590.00 Hz | 0.00 | Fixed frequency added to the reference when the ADD input is on. |
| A154 | Deceleration stop frequency | 0.00 off or start freq to 590.00 Hz | 0.00 | Frequency at which deceleration pauses (hold). |
| A156 | PID sleep operation level | 0.00-590.00 Hz | 0.00 | Frequency below which PID sleep may begin. |
| b001 | Power interruption/undervoltage restart selection | 00 trip, 01 0-Hz restart, 02 pull-in restart at shutoff, 03 trip after pull-in decel stop, 04 pull-in restart | 00 | What the drive does after a brief power loss: trip or restart in some way. |
| b002 | Allowable power interruption time | 0.3-25.0 s | 1.0 | Longest power dip that the drive will ride through. |
| b003 | Restart standby time | 0.3-100.0 s | 1.0 | Wait before restart after a power interruption. |
| b004 | Undervoltage trip selection during stop | 00 off, 01 on, 02 off during stop and RUN-off decel stop | 00 | Whether undervoltage trips when stopped. |
| b005 | Power interruption restart count | 00 16 times, 01 unlimited | 00 | Number of automatic restarts allowed after power dips. |
| b008 | Overvoltage/overcurrent restart selection | 00 trip, 01 0-Hz, 02 pull-in at shutoff, 03 trip after pull-in decel stop, 04 pull-in restart | 00 | Automatic retry behaviour after overvoltage or overcurrent trips. |
| b010 | Overvoltage/overcurrent restart count | 1-3 | 3 | How many retries are allowed. |
| b011 | Overvoltage/overcurrent restart standby time | 0.3-100.0 s | 1.0 | Delay before an automatic retry. |
| b012 | 1st electronic thermal level | 0.20 x rated current to 1.00 x rated current (A) | Inverter rated current | Motor overload trip current; set to the motor nameplate current. |
| b212 | 2nd electronic thermal level | 0.20 x rated to 1.00 x rated (A) | Inverter rated current | Thermal level for the second motor. |
| b013 | 1st electronic thermal characteristics selection | 00 reduced torque, 01 constant torque, 02 free setting | 01 | Matches the thermal curve to the load type. |
| b021 | 1st overload limit selection | 00 off, 01 accel+constant, 02 constant only, 03 accel+constant (accelerate in regen) | 01 | Enables current limiting that reduces frequency when current goes too high. |
| b022 | 1st overload limit level | 0.20 x rated to 2.00 x rated (A, normal load) | Rated x 1.50 (normal) / 1.20 (light) | Current threshold at which the limiter acts. |
| b023 | 1st overload limit parameter | 0.1-3000.0 s | 1.0 | Deceleration time used while the limiter is active. |
| b027 | Overcurrent suppression selection | 00 off, 01 on, 02 on at reduced voltage startup | 01 | Suppresses overcurrent trips by limiting the ramp. |
| b028 | Frequency pull-in restart level | 0.20 x rated to 2.00 x rated (A) | Inverter rated current | Current limit while pulling in to a spinning motor. |
| b029 | Frequency pull-in restart parameter | 0.1-3000.0 s | 0.5 | Deceleration rate during pull-in. |
| b030 | Starting frequency selection at pull-in restart | 00 frequency at interruption, 01 maximum, 02 set frequency | 00 | Where the search for a spinning motor starts. |
| b031 | Soft lock selection | 00-03 | 01 | Write-protects parameters; if you cannot change data, check this. |
| b033 | Motor cable length | 5-20 | 10. | Cable length parameter used by the inverter's control. |
| b034 | RUN time/power ON time detection level | 0 off, 1-65535 (x10 h) | 0. | Threshold for the RNT/ONT maintenance signals. |
| b035 | RUN direction limit selection | 00 none, 01 forward only, 02 reverse only | 00 | Blocks one rotation direction. |
| b036 | Reduced voltage startup selection | 0 off, 1 (short) to 255 (long) | 2 | Slows voltage build-up at start to reduce inrush. |
| b037 | Display selection | 00 complete, 01 function-specific, 02 user, 03 data comparison, 05 monitor | 00 | Controls which parameters show on the keypad; set to 00 if one is missing. |
| b038 | Initial screen selection | 000, 001-060 (d001-d060), 201 (F001) | 001 | Which screen appears at power-up. |
| b040 | Torque limit selection | 00 four-quadrant setting, 01 terminal switching, 02 analog voltage, 03 option | 00 | How torque limits are chosen. |
| b041 | Torque limit 1 (forward power running) | 0-200 %, 255 off | 200. | Torque limit in forward motoring. |
| b049 | Normal/light load selection | 00 normal (ND), 01 light (LD) | 00 | Selects the load rating, which changes available current and carrier frequency. |
| b050 | Deceleration stop on power interruption selection | 00 off, 01 decel stop, 02 constant voltage no recovery, 03 constant voltage with recovery | 00 | Ride-through by decelerating on mains loss. |
| b070 | Analog operation level at FV disconnection | 0-100 %, 255 off | no | Speed level used if the FV signal is lost. |
| b071 | Analog operation level at FI disconnection | 0-100 %, 255 off | no | Speed level used if the FI signal is lost. |
| b075 | Ambient temperature | 10-50 degC | 40 | Ambient temperature used for life estimation. |
| b078 | Integrated power clear | 00 disabled, 01 clear with Enter | 00 | Resets the kWh counter. |
| b082 | Starting frequency | 0.01-10.00 Hz (100.00 in HF mode) | 1.50 | Frequency at which output begins at start. |
| b083 | Carrier frequency | 2.0-15.0 / 10.0 kHz (normal/light) | 10.0 / 2.0 in HF mode | PWM switching frequency; high values reduce motor noise but increase heat and leakage and need derating. |
| b084 | Initialization selection | 00 off, 01 clear fault monitor, 02 initialise data, 03 clear faults and initialise, 04 clear faults, initialise and clear DriveProgramming | 00 | Chooses what to reset. |
| b086 | Frequency conversion coefficient | 0.01-99.99 | 1.00 | Scale used for d007 display. |
| b087 | STOP key selection | 00 enabled, 01 disabled, 02 only reset enabled | 00 | Whether the keypad STOP key works when running from terminals. |
| b088 | Free-run stop selection | 00 0-Hz restart, 01 pull-in at shutoff, 02 pull-in restart | 00 | How the drive restarts after a free-run stop is released. |
| b089 | Automatic carrier reduction | 00 off, 01 on (current), 02 on (fin temperature) | 01 | Lowers carrier frequency to avoid overheating. |
| b090 | Usage rate of regenerative braking | 0.0 off, 0.1-100.0 % | 0.0 | Duty rating of the braking resistor; exceeding it trips E06. |
| b091 | Stop selection | 00 deceleration stop, 01 free-run stop | 00 | What happens when RUN is removed. |
| b092 | Cooling fan operation | 00 always, 01 only when running, 02 by fin temperature | 01 | Fan control; set to always if overheating. |
| b093 | Total fan operation time clear | 00 off, 01 clear | 00 | Reset fan hours after replacement. |
| b094 | Initialization target setting | 00 all, 01 all except terminals/comms, 02 U registration only, 03 all except U and b37 | 00 | Selects the scope of the initialisation. |
| b095 | Regenerative braking selection | 00 off, 01 on (not when stopped), 02 on always | 00 | Enables the braking chopper. |
| b096 | Regenerative braking ON level | 200 V: 330-400 V, 400 V: 660-800 V | 360. / 720. | DC bus voltage where braking resistor turns on. |
| b097 | Braking resistor value | Min. resistance to 600.0 ohm | Minimum resistance | Resistor value for overload protection. |
| b098 | Ground fault detection selection | 00 off, 01 on | 01 | Enables earth fault check at power-up (E14). |
| b100 | Free V/f frequency 1 (b100-b113: pairs 1-7) | 0 off, 1 to next frequency (Hz) | 0. | Free-form V/f curve points; frequency 7 must be at least 30 Hz. |
| b120 | Brake control function selection | 00 off, 01 on (DC brake at stop), 02 on (no DC brake at stop) | 00 | Enables lifting-style brake sequence. |
| b121 | Brake release wait time | 0.00-5.00 s | 0.00 | Delay before brake release. |
| b124 | Brake error detection time | 0.00-5.00 s | 0.00 | Time to wait for brake confirmation before E36. |
| b125 | Brake release frequency | 0.00-590.00 Hz | 0.00 | Frequency at which the brake is released. |
| b126 | Brake release current | 0.00-2.00 x rated (A) | Inverter rated current | Current threshold for brake release. |
| b130 | Overvoltage suppression selection during decel | 00 off, 01 on (constant DC), 02 on (accel allowed) | 01 | Stretches the deceleration to keep the DC bus under control; helps with E07. |
| b131 | Overvoltage suppression level during decel | 200 V: 330-400 V, 400 V: 660-800 V | 380. / 760. | DC bus level at which suppression acts. |
| b133 | Overvoltage suppression P gain during decel | 0.00-5.00 | 0.20 | Proportional gain. |
| b134 | Overvoltage suppression I time during decel | 0.0-150.0 s | 1.0 | Integral time. |
| b145 | GS input operation selection | 00 no trip, 01 trip | 00 | Whether opening safety inputs causes E37. |
| b165 | Operation on external operator disconnection | 00 trip, 01 trip after decel, 02 ignore, 03 free-run, 04 decel stop | 02 | Reaction to loss of remote operator. |
| b171 | Inverter mode selection | 00 unset, 01 induction, 02 induction high-frequency, 03 PM motor | 00 | Selects motor type mode; changes defaults. |
| b180 | Initialization execution | 00 off, 01 execute | 00 | Starts initialisation when set to 01. |
| b190 | Password A setting | 0000 off, 0001-FFFF | 0000 | Parameter password. |
| b910 | Motor electronic thermal selection | 00 off, 01 fixed, 02 b911 ratio, 03 b912 time | 03 | Selects the thermal model for motor vs inverter protection. |
| b911 | Motor electronic thermal subtraction ratio | 0.10-100000.00 s | 600.00 | Subtraction time for thermal model. |
| b912 | Motor electronic thermal subtraction time constant | 0.10-100000.00 s | 120.00 | Time constant of thermal subtraction. |
| b913 | Motor electronic thermal integration gain | 1.0-200.0 % | 100.0 | Gain of the thermal integration. |
| b914 | Electronic thermal load rate at power-off | 00 off, 01 on | 01 | Keeps thermal state across power off. |
| C001 | Multi-function input S1 selection | 00 FW,01 RV,02-05 CF1-4,06 JG,07 DB,08 SET,09 2CH,11 FRS,12 EXT,13 USP,14 CS,15 SFT,16 AT,18 RS,19 TH,20 STA,21 STP,22 F/R,23 PID,24 PIDC,27-29 UP/DWN/UDC,31 OPE,32-38 SF1-7,39 OLR,40 TL,41-42 TRQ,44 BOK,46 LAC,47 PCLR,50 ADD,51 F-TM,52 ATR,53 KHC,56-62 MI1-7,65 AHD,66-68 CP1-3,69 ORL,70 ORG,73 SPD,81 485,82 PRG,83 HLD,84 ROK,85 EB,86 DISP,91 PSET,255 no | 00 (FW) | Function assigned to control terminal S1. |
| C002 | Multi-function input S2 selection | 00 FW,01 RV,02-05 CF1-4,06 JG,07 DB,08 SET,09 2CH,11 FRS,12 EXT,13 USP,14 CS,15 SFT,16 AT,18 RS,19 TH,20 STA,21 STP,22 F/R,23 PID,24 PIDC,27-29 UP/DWN/UDC,31 OPE,32-38 SF1-7,39 OLR,40 TL,41-42 TRQ,44 BOK,46 LAC,47 PCLR,50 ADD,51 F-TM,52 ATR,53 KHC,56-62 MI1-7,65 AHD,66-68 CP1-3,69 ORL,70 ORG,73 SPD,81 485,82 PRG,83 HLD,84 ROK,85 EB,86 DISP,91 PSET,255 no | 01 (RV) | Function assigned to control terminal S2. |
| C003 | Multi-function input S3 selection | 00 FW,01 RV,02-05 CF1-4,06 JG,07 DB,08 SET,09 2CH,11 FRS,12 EXT,13 USP,14 CS,15 SFT,16 AT,18 RS,19 TH,20 STA,21 STP,22 F/R,23 PID,24 PIDC,27-29 UP/DWN/UDC,31 OPE,32-38 SF1-7,39 OLR,40 TL,41-42 TRQ,44 BOK,46 LAC,47 PCLR,50 ADD,51 F-TM,52 ATR,53 KHC,56-62 MI1-7,65 AHD,66-68 CP1-3,69 ORL,70 ORG,73 SPD,81 485,82 PRG,83 HLD,84 ROK,85 EB,86 DISP,91 PSET,255 no | 18 (RS) | Function assigned to control terminal S3. |
| C004 | Multi-function input S4 selection | 00 FW,01 RV,02-05 CF1-4,06 JG,07 DB,08 SET,09 2CH,11 FRS,12 EXT,13 USP,14 CS,15 SFT,16 AT,18 RS,19 TH,20 STA,21 STP,22 F/R,23 PID,24 PIDC,27-29 UP/DWN/UDC,31 OPE,32-38 SF1-7,39 OLR,40 TL,41-42 TRQ,44 BOK,46 LAC,47 PCLR,50 ADD,51 F-TM,52 ATR,53 KHC,56-62 MI1-7,65 AHD,66-68 CP1-3,69 ORL,70 ORG,73 SPD,81 485,82 PRG,83 HLD,84 ROK,85 EB,86 DISP,91 PSET,255 no | 12 (EXT) | Function assigned to control terminal S4. |
| C005 | Multi-function input S5 selection | 00 FW,01 RV,02-05 CF1-4,06 JG,07 DB,08 SET,09 2CH,11 FRS,12 EXT,13 USP,14 CS,15 SFT,16 AT,18 RS,19 TH,20 STA,21 STP,22 F/R,23 PID,24 PIDC,27-29 UP/DWN/UDC,31 OPE,32-38 SF1-7,39 OLR,40 TL,41-42 TRQ,44 BOK,46 LAC,47 PCLR,50 ADD,51 F-TM,52 ATR,53 KHC,56-62 MI1-7,65 AHD,66-68 CP1-3,69 ORL,70 ORG,73 SPD,81 485,82 PRG,83 HLD,84 ROK,85 EB,86 DISP,91 PSET,255 no | 02 (CF1) | Function assigned to control terminal S5. |
| C006 | Multi-function input S6 selection | 00 FW,01 RV,02-05 CF1-4,06 JG,07 DB,08 SET,09 2CH,11 FRS,12 EXT,13 USP,14 CS,15 SFT,16 AT,18 RS,19 TH,20 STA,21 STP,22 F/R,23 PID,24 PIDC,27-29 UP/DWN/UDC,31 OPE,32-38 SF1-7,39 OLR,40 TL,41-42 TRQ,44 BOK,46 LAC,47 PCLR,50 ADD,51 F-TM,52 ATR,53 KHC,56-62 MI1-7,65 AHD,66-68 CP1-3,69 ORL,70 ORG,73 SPD,81 485,82 PRG,83 HLD,84 ROK,85 EB,86 DISP,91 PSET,255 no | 03 (CF2) | Function assigned to control terminal S6. |
| C007 | Multi-function input S7 selection | 00 FW,01 RV,02-05 CF1-4,06 JG,07 DB,08 SET,09 2CH,11 FRS,12 EXT,13 USP,14 CS,15 SFT,16 AT,18 RS,19 TH,20 STA,21 STP,22 F/R,23 PID,24 PIDC,27-29 UP/DWN/UDC,31 OPE,32-38 SF1-7,39 OLR,40 TL,41-42 TRQ,44 BOK,46 LAC,47 PCLR,50 ADD,51 F-TM,52 ATR,53 KHC,56-62 MI1-7,65 AHD,66-68 CP1-3,69 ORL,70 ORG,73 SPD,81 485,82 PRG,83 HLD,84 ROK,85 EB,86 DISP,91 PSET,255 no | 06 (JG) | Function assigned to control terminal S7. |
| C011 | Multi-function input S1 operation selection | 00 NO, 01 NC | 00 | Contact logic (normally open or closed) for input S1. |
| C012 | Multi-function input S2 operation selection | 00 NO, 01 NC | 00 | Contact logic (normally open or closed) for input S2. |
| C013 | Multi-function input S3 operation selection | 00 NO, 01 NC | 00 | Contact logic (normally open or closed) for input S3. |
| C014 | Multi-function input S4 operation selection | 00 NO, 01 NC | 00 | Contact logic (normally open or closed) for input S4. |
| C015 | Multi-function input S5 operation selection | 00 NO, 01 NC | 00 | Contact logic (normally open or closed) for input S5. |
| C016 | Multi-function input S6 operation selection | 00 NO, 01 NC | 00 | Contact logic (normally open or closed) for input S6. |
| C017 | Multi-function input S7 operation selection | 00 NO, 01 NC | 00 | Contact logic (normally open or closed) for input S7. |
| C021 | Multi-function output P1 selection | 00 RUN,01 FA1,02 FA2,03 OL,04 OD,05 AL,06 FA3,07 OTQ,09 UV,10 TRQ,11 RNT,12 ONT,13 THM,19 BRK,20 BER,21 ZS,22 DSE,23 POK,24 FA4,25 FA5,26 OL2,27 FVDc,28 FIDc,31 FBV,32 NDc,33-35 LOG1-3,39 WAC,40 WAF,41 FR,42 OHF,43 LOC,44-46 MO1-3,50 IRDY,51 FWR,52 RVR,53 MJA,54 WCFV,55 WCFI,58 FREF,59 REF,60 SETM,62 EDM,63 OPO,255 no | 00 (RUN) | Function of open-collector output P1. |
| C022 | Multi-function output P2 selection | same as C021 | 01 (FA1) | Function of open-collector output P2. |
| C026 | Multi-function relay output (MA, MB) selection | same as C021 | 05 (AL) | Function of the relay; default is the alarm signal. |
| C027 | MP selection | 00-16 (output freq, current, torque, ... 07 LAD freq, etc.) | 07 | Quantity on the pulse monitor output. |
| C028 | AM selection | 00-16 (frequency, current, torque, voltage, power, thermal ...) | 07 | Quantity on the analog monitor output. |
| C030 | Digital current monitor reference value | 0.20 x rated to 2.00 x rated (A) | Inverter rated current | Current that equals full-scale pulse output. |
| C031 | Multi-function output P1 operation selection | 00 NO, 01 NC | 00 | Contact logic of P1. |
| C032 | Multi-function output P2 operation selection | 00 NO, 01 NC | 00 | Contact logic of P2. |
| C036 | Multi-function relay output operation selection | 00 NO, 01 NC | 01 | Contact logic of the relay. |
| C038 | Low current signal output selection | 00 accel/decel and constant, 01 constant only | 01 | When the low-current output is active. |
| C039 | Low current detection level | 0.00 to 2.00 x rated (A) | Inverter rated current | Threshold for the low-current signal (LOC). |
| C041 | 1st overload warning level | 0.00 (off), 0.01 to 2.00 x rated (A) | Rated x 1.15 | Current at which the overload warning (OL) output turns on. |
| C042 | Arrival frequency during acceleration 1 | 0.00 off, 0.01-590.00 Hz | 0.00 | Frequency for the accel-arrival signal. |
| C043 | Arrival frequency during deceleration 1 | 0.00 off, 0.01-590.00 Hz | 0.00 | Frequency for the decel-arrival signal. |
| C044 | PID deviation excessive level | 0.0-100.0 % | 3.0 | Deviation level for the OD output. |
| C054 | Overtorque/undertorque selection | 00 over, 01 under | 00 | Whether OTQ signals over- or under-torque. |
| C055 | Overtorque/undertorque level (forward power running) | 0-200 % | 100. | Threshold for the OTQ signal. |
| C061 | Electronic thermal warning level | 0-100 % | 90. | Thermal load percent for the THM warning output. |
| C063 | 0 Hz detection level | 0.00-100.00 Hz | 0.00 | Frequency below which the ZS signal is on. |
| C064 | Cooling fin overheat warning level | 0-110 degC | 100. | Fin temperature for the OHF warning. |
| C071 | Communication speed selection (baud rate) | 03 2400, 04 4800, 05 9600, 06 19.2k, 07 38.4k, 08 57.6k, 09 76.8k, 10 115.2k bps | 05 | Serial baud rate for Modbus RTU on the RS-485 port. |
| C072 | Communication station number selection | 1-247 | 1. | Modbus slave address. |
| C074 | Communication parity selection | 00 none, 01 even, 02 odd | 00 | Parity of the serial port. |
| C075 | Communication stop bit selection | 1, 2 | 1 | Stop bits of the serial port. |
| C076 | Operation selection on communication error | 00 trip, 01 trip after decel, 02 ignore, 03 free-run, 04 decel stop | 02 | Reaction to a comms timeout; set 00 to produce E41. |
| C077 | Communication error timeout time | 0.00 off, 0.01-99.99 s | 0.00 | How long without messages counts as a comms error. |
| C078 | Communication wait time | 0-1000 ms | 0. | Delay before replying to Modbus requests. |
| C081 | FV adjustment | 0.0-200.0 % | 100.0 | Trim for the FV analog input. |
| C082 | FI adjustment | 0.0-200.0 % | 100.0 | Trim for the FI analog input. |
| C085 | Thermistor adjustment | 0.0-200.0 % | 100.0 | Trim for the thermistor input level. |
| C096 | Communication selection | 00 Modbus, 01 co-inverter, 02 co-inverter manager | 00 | Role of the RS-485 port. |
| C101 | UP/DWN storage selection | 00 not stored, 01 stored | 00 | Whether UP/DWN remote-set speed survives power-off. |
| C102 | Reset selection | 00 reset at power-on, 01 reset at power-off, 02 only during trip, 03 trip reset only | 02 | When the RS input resets the drive. |
| C103 | Reset restart selection | 00 0-Hz restart, 01 pull-in at shutoff, 02 pull-in restart | 00 | Restart mode after reset. |
| C111 | 1st overload warning level 2 | 0.00 off, 0.01 to 2.00 x rated (A) | Rated x 1.15 | Second overload warning level. |
| C130 | Multi-function output P1 ON delay time | 0.0-100.0 s | 0.0 | Delay before P1 turns on (similar C131-C141 for OFF delays and others). |
| C160 | Multi-function input S1 response time | 0-200 (x2 ms) | 1. | Debounce time of input S1 (C160-C166 for S1-S7). |
| H001 | Auto-tuning selection | 00 off, 01 on (no rotation), 02 on (with rotation) | 00 | Starts the motor auto-tune used by sensorless vector control. |
| H002 | 1st motor parameter selection | 00 standard, 02 auto-tuning data | 00 | Which motor constant set is used. |
| H003 | 1st motor capacity | 0.1-18.5 kW (series) | Max applicable motor capacity | Motor kW rating setting. |
| H004 | 1st motor pole number | 2/4/6/8 poles | 4 | Number of motor poles, needed for speed display. |
| H005 | 1st speed response | 1-1000 | 100. | Responsiveness of the speed control. |
| H006 | 1st stabilization parameter | 0-255 | 100. | Damping of hunting. |
| H007 | 1st motor rated current | 0.01-655.35 A | Rated output current (normal load) | Motor nameplate current, used for tuning. |
| H020 | 1st motor parameter R1 | 0.001-65.535 ohm | Depends on capacity | Primary winding resistance. |
| H021 | 1st motor parameter R2 | 0.001-65.535 ohm | Depends on capacity | Secondary resistance. |
| H022 | 1st motor parameter L | 0.01-655.35 mH | Depends on capacity | Leakage inductance. |
| H023 | 1st motor parameter Io | 0.01-655.35 A | Depends on capacity | No-load current. |
| H024 | 1st motor parameter J | 0.001-9999.000 kgm2 | Depends on capacity | Moment of inertia. |
| H030 | 1st motor parameter R1 (auto-tuning) | 0.001-65.535 ohm | Depends on capacity | R1 measured by auto-tuning. |
| H033 | 1st motor parameter Io (auto-tuning) | 0.01-655.35 A | Depends on capacity | No-load current measured by auto-tuning. |
| H050 | Speed feedback slip compensation P gain | 0.00-10.00 | 0.20 | Proportional gain for V/f with feedback. |
| H051 | Speed feedback slip compensation I gain | 0-1000 s | 2. | Integral gain. |
| H102 | PM motor parameter selection | 00 standard, 01 auto-tuning | 00 | Source of PM motor constants. |
| H103 | PM motor capacity | 0.1-18.5 kW | Max applicable | PM motor power. |
| H104 | PM motor pole number | 2/4/6/8 | Depends on capacity | PM motor poles. |
| H105 | PM motor rated current | 0.00-1.00 x rated | Depends on capacity | PM motor current. |
| H117 | PM motor starting current | 20.00-100.00 % | 70.00 | Current at start. |
| H123 | PM motor starting method selection | 00 off, 01 initial pole position estimation | 00 | Start method for PM motors. |
| P001 | Operation selection on option error | 00 trip, 01 continue | 00 | Reaction to an option error. |
| P003 | Pulse train input RP selection | 00 frequency, 01 feedback pulse, 02 MI8 | 00 | Role of the RP input. |
| P004 | Pulse train input type selection | 00 single, 01 90-degree, 03 single+direction | 00 | Pulse train format. |
| P011 | Number of encoder pulses | 32-1024 pulses | 512. | Encoder resolution. |
| P012 | Simple position control selection | 00 off, 02 on | 00 | Enables simple positioning. |
| P015 | Creep speed setting | Start freq to 10.00 Hz (100.00 in HF mode) | 5.00 | Slow speed near target. |
| P026 | Overspeed error detection level | 0.0-150.0 % | 115.0 | Threshold for E81. |
| P027 | Speed deviation excessive level | 0.00-120.00 Hz | 10.00 | Deviation limit for DSE. |
| P031 | Acceleration/deceleration time input type | 00 operator, 03 DriveProgramming | 00 | Source of ramp times. |
| P033 | Torque reference input selection | 00 FV, 01 FI, 03 operator, 06 option | 00 | Source of torque reference. |
| P034 | Torque reference setting | 0-200 % | 0. | Fixed torque reference. |
| P077 | Encoder disconnection detection time | 0.0 off, 0.1-10.0 s | 1.0 | Time before E80. |
| P200 | Modbus mapping function selection | 00 standard, 01 mapping on | 00 | Enables register remapping. |
| P400 | Modbus mapping endian selection | 00 big, 01 little, 02 special | 00 | Byte order for mapped registers. |
See also the Omron MX2 fault codes. ServMod reads, compares and backs up these parameters from your phone: how to connect.
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.