Omron MX2 fault codes: meaning and checks

36 fault and warning codes of the Omron MX2, each with what it means and what to check first. Tap a code for the full checklist.

CodeNameMeaning
E01Overcurrent at constant speedOutput current spiked to roughly twice the inverter rating while running at steady speed, so the output was...
E02Overcurrent during decelerationOutput current spiked to roughly twice the inverter rating while slowing down.
E03Overcurrent during accelerationOutput current spiked to roughly twice the inverter rating while speeding up.
E04Overcurrent in other conditionsOvercurrent trip outside the accel, decel and constant-speed cases.
E05Motor overload (electronic thermal)The built-in electronic thermal model decided the motor was overloaded. With the separated thermal setting...
E06Braking resistor overloadRegenerative braking circuit usage went above the limit set in b090.
E07Overvoltage (DC bus)DC bus voltage rose above the trip level (about 400 V on 200 V class, 800 V on 400 V class) because of...
E08EEPROM errorFault while accessing the internal EEPROM, often from noise or excessive temperature. Cannot be reset by RS...
E09UndervoltageDC bus voltage fell below the undervoltage level (about 173 V on 200 V class, 345 V on 400 V class).
E10Current detector errorThe inverter detected a fault in its current sensing circuit.
E11CPU errorMalfunction or error in the internal CPU. Cannot be reset by RS terminal or STOP/RESET key; power cycle is...
E12External tripA multi-function input programmed as EXT (12) turned ON.
E13USP errorPower was applied while a RUN command was already present, with the USP function enabled.
E14Ground faultAn earth fault was detected between inverter output and motor at power-up. Cannot be reset by RS terminal or...
E15Input overvoltageSupply voltage stayed high (DC bus about 390 V on 200 V class, 780 V on 400 V class) for 100 seconds.
E19Temperature sensor errorThe heat sink temperature sensing circuit reports an error such as a broken sensor line.
E21OvertemperatureMain circuit temperature exceeded the allowed limit.
E22CPU communication errorFault or malfunction in the internal CPU communication.
E25Main circuit errorAn error was detected on the main circuit board.
E26Analog current input errorExcess current flowed into the FI analog current input terminal.
E30Driver errorThe gate driver detected a momentary overcurrent (around 350% of rated), main-element overtemperature or...
E35Thermistor errorThe external thermistor input reads an abnormal motor temperature.
E36Brake errorWith brake control enabled (b120 = 01), the brake ON/OFF confirmation did not arrive within b124 after the...
E37Emergency shutoff (safety input)The safety inputs GS1/GS2 were opened.
E38Low-speed overloadThe electronic thermal function detected an overload at extremely low speed (0.2 Hz or less); with the...
E40Digital Operator connection errorCommunication with the remote operator 3G3AX-OP01 failed or the cable was disconnected (detection can be...
E41Modbus communication errorA communication timeout occurred while C076 is set to trip.
E43-E45DriveProgramming program errorErrors raised by the built-in DriveProgramming function (program faults).
E50-E59DriveProgramming user tripUser-defined trips generated by a DriveProgramming program.
E60-E68Option unit errorError reported by an installed option unit (for example the EtherCAT unit).
E69Option communication timeoutCommunication between the inverter and the option unit timed out.
E80Encoder disconnectionMeasured motor speed stayed below the starting frequency (b082) for the P077 time while output was at or...
E81OverspeedMotor speed from the encoder exceeded the P026 level (P026 not zero); d008 is set to 0.
E83Position control range tripDuring simple position control the current position went outside the limits P072/P073.
E99STO self-diagnosis errorA fault was found in the STO input terminals or internal safety circuit; independent of the b145 setting.
WARNParameter conflict warningWhen one setting contradicts another (for example a frequency limit above the maximum frequency, or a start...

Source: 3G3MX2-V2 User's Manual (I666-E1-03, August 2024). Manufacturer page. See also the Omron MX2 parameter list, the connection and backup page and the wiring diagrams.

Download free for Android

This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.