Omron MX2 fault codes: meaning and checks
36 fault and warning codes of the Omron MX2, each with what it means and what to check first. Tap a code for the full checklist.
| Code | Name | Meaning |
|---|---|---|
| E01 | Overcurrent at constant speed | Output current spiked to roughly twice the inverter rating while running at steady speed, so the output was... |
| E02 | Overcurrent during deceleration | Output current spiked to roughly twice the inverter rating while slowing down. |
| E03 | Overcurrent during acceleration | Output current spiked to roughly twice the inverter rating while speeding up. |
| E04 | Overcurrent in other conditions | Overcurrent trip outside the accel, decel and constant-speed cases. |
| E05 | Motor overload (electronic thermal) | The built-in electronic thermal model decided the motor was overloaded. With the separated thermal setting... |
| E06 | Braking resistor overload | Regenerative braking circuit usage went above the limit set in b090. |
| E07 | Overvoltage (DC bus) | DC bus voltage rose above the trip level (about 400 V on 200 V class, 800 V on 400 V class) because of... |
| E08 | EEPROM error | Fault while accessing the internal EEPROM, often from noise or excessive temperature. Cannot be reset by RS... |
| E09 | Undervoltage | DC bus voltage fell below the undervoltage level (about 173 V on 200 V class, 345 V on 400 V class). |
| E10 | Current detector error | The inverter detected a fault in its current sensing circuit. |
| E11 | CPU error | Malfunction or error in the internal CPU. Cannot be reset by RS terminal or STOP/RESET key; power cycle is... |
| E12 | External trip | A multi-function input programmed as EXT (12) turned ON. |
| E13 | USP error | Power was applied while a RUN command was already present, with the USP function enabled. |
| E14 | Ground fault | An earth fault was detected between inverter output and motor at power-up. Cannot be reset by RS terminal or... |
| E15 | Input overvoltage | Supply voltage stayed high (DC bus about 390 V on 200 V class, 780 V on 400 V class) for 100 seconds. |
| E19 | Temperature sensor error | The heat sink temperature sensing circuit reports an error such as a broken sensor line. |
| E21 | Overtemperature | Main circuit temperature exceeded the allowed limit. |
| E22 | CPU communication error | Fault or malfunction in the internal CPU communication. |
| E25 | Main circuit error | An error was detected on the main circuit board. |
| E26 | Analog current input error | Excess current flowed into the FI analog current input terminal. |
| E30 | Driver error | The gate driver detected a momentary overcurrent (around 350% of rated), main-element overtemperature or... |
| E35 | Thermistor error | The external thermistor input reads an abnormal motor temperature. |
| E36 | Brake error | With brake control enabled (b120 = 01), the brake ON/OFF confirmation did not arrive within b124 after the... |
| E37 | Emergency shutoff (safety input) | The safety inputs GS1/GS2 were opened. |
| E38 | Low-speed overload | The electronic thermal function detected an overload at extremely low speed (0.2 Hz or less); with the... |
| E40 | Digital Operator connection error | Communication with the remote operator 3G3AX-OP01 failed or the cable was disconnected (detection can be... |
| E41 | Modbus communication error | A communication timeout occurred while C076 is set to trip. |
| E43-E45 | DriveProgramming program error | Errors raised by the built-in DriveProgramming function (program faults). |
| E50-E59 | DriveProgramming user trip | User-defined trips generated by a DriveProgramming program. |
| E60-E68 | Option unit error | Error reported by an installed option unit (for example the EtherCAT unit). |
| E69 | Option communication timeout | Communication between the inverter and the option unit timed out. |
| E80 | Encoder disconnection | Measured motor speed stayed below the starting frequency (b082) for the P077 time while output was at or... |
| E81 | Overspeed | Motor speed from the encoder exceeded the P026 level (P026 not zero); d008 is set to 0. |
| E83 | Position control range trip | During simple position control the current position went outside the limits P072/P073. |
| E99 | STO self-diagnosis error | A fault was found in the STO input terminals or internal safety circuit; independent of the b145 setting. |
| WARN | Parameter conflict warning | When one setting contradicts another (for example a frequency limit above the maximum frequency, or a start... |
Source: 3G3MX2-V2 User's Manual (I666-E1-03, August 2024). Manufacturer page. See also the Omron MX2 parameter list, the connection and backup page and the wiring diagrams.
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.