Omron MX2 fault E01: Overcurrent at constant speed

Output current spiked to roughly twice the inverter rating while running at steady speed, so the output was cut.

What to check

  1. Look for sudden load changes and remove them
  2. Check motor leads for short circuit between phases
  3. Check motor and cable for an earth fault
  4. Check the motor is not seized or locked
  5. If a PM motor is used, confirm its parameters were set and tuned correctly

Source: 3G3MX2-V2 User's Manual (I666-E1-03, August 2024), page 572. Manufacturer page.

Keep the settings safe before you change anything

Before you reset, replace or reprogram a Omron MX2, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Omron MX2 to a phone and the wiring diagrams.

Download free for Android

Other Omron MX2 fault codes

E01E02E03E04E05E06E07E08E09E10E11E12E13E14E15E19E21E22E25E26E30E35E36E37E38E40E41E43-E45E50-E59E60-E68E69E80E81E83E99WARN

This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.