Omron MX2 fault WARN: Parameter conflict warning

When one setting contradicts another (for example a frequency limit above the maximum frequency, or a start frequency above a limit) the PRG LED blinks and the RUN command is ignored. The latest warning code is stored in d090.

What to check

  1. Read d090 to see which parameter pair conflicts
  2. Correct the settings: frequency upper/lower limits (A061/A062) vs maximum frequency (A004), start frequency (b082) vs limits and jogging, set frequency vs jump frequencies

Source: 3G3MX2-V2 User's Manual (I666-E1-03, August 2024), page 579. Manufacturer page.

Keep the settings safe before you change anything

Before you reset, replace or reprogram a Omron MX2, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Omron MX2 to a phone and the wiring diagrams.

Download free for Android

Other Omron MX2 fault codes

E01E02E03E04E05E06E07E08E09E10E11E12E13E14E15E19E21E22E25E26E30E35E36E37E38E40E41E43-E45E50-E59E60-E68E69E80E81E83E99WARN

This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.