Fault codes / Omron MX2 / E09
Omron MX2 fault E09: Undervoltage
DC bus voltage fell below the undervoltage level (about 173 V on 200 V class, 345 V on 400 V class).
What to check
- Check supply voltage
- Check supply capacity is sufficient for the load/starting
- Consider ageing of the DC bus capacitors
Source: 3G3MX2-V2 User's Manual (I666-E1-03, August 2024), page 573. Manufacturer page.
Keep the settings safe before you change anything
Before you reset, replace or reprogram a Omron MX2, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Omron MX2 to a phone and the wiring diagrams.
Other Omron MX2 fault codes
E01E02E03E04E05E06E07E08E09E10E11E12E13E14E15E19E21E22E25E26E30E35E36E37E38E40E41E43-E45E50-E59E60-E68E69E80E81E83E99WARN
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.