211 parameters of the Hitachi WJ200 with range, default value and a short description. Source: WJ200 Series Quick Reference Guide (NT3381AX, April 2016).
| No. | Name | Range | Default | What it does |
|---|---|---|---|---|
| d001 | Output frequency monitor | 0.00 to 400.0 (580.0) Hz | - | Live frequency the drive is sending to the motor. Handy for checking the drive is following the command. |
| d002 | Output current monitor | 0.0 to 655.3 A | - | Filtered motor current; compare with nameplate to spot overload or no-load conditions. |
| d003 | Rotation direction monitor | F / o / r | - | Shows forward, stop or reverse. |
| d004 | PID feedback (PV) monitor | 0.00 to 10000 | - | Scaled process variable used by the PID loop (scaled by A075). |
| d005 | Intelligent input terminal status | bit display | - | Shows which of the programmable input terminals are currently ON; useful for checking wiring. |
| d006 | Intelligent output terminal status | bit display | - | Shows which programmable output terminals and relay are ON. |
| d013 | Output voltage monitor | 0.0 to 600.0 V | - | Voltage being applied to the motor. |
| d016 | Elapsed RUN time monitor | 0 to 99,900 h | - | Total hours the drive has been in run mode. |
| d017 | Elapsed power-on time monitor | 0 to 99,900 h | - | Total hours the drive has been powered. |
| d018 | Heat sink temperature monitor | -20 to 150 C | - | Cooling fin temperature; check this when diagnosing E21 over-temperature trips. |
| d022 | Life check monitor | bit display | - | Indicates whether the electrolytic capacitors or the cooling fan have reached their life limit. |
| d050 | Dual monitor | per b160 / b161 | - | Shows two chosen d-monitors, switched with the up/down keys. |
| d060 | Inverter mode monitor | I-C / I-V / H-I / P | - | Shows the active drive mode: induction CT, induction VT, high-frequency, or permanent magnet. |
| d062 | Frequency source monitor | code | - | Shows where the frequency reference is currently coming from (operator, multi-speed, Modbus, analog input, etc.). Available from version 3.0. |
| d063 | Run command source monitor | 1 to 4 | - | Shows the active run command source: terminal, operator, Modbus or option. Available from version 3.0. |
| d080 | Trip counter | 0 to 65530 | - | Number of trips recorded since the history was last cleared. |
| d081 | Trip monitor 1 (latest) | - | - | Detail of the most recent trip: code, frequency, current, DC bus voltage and run/power-on hours at that moment. d082-d086 hold the five earlier trips. |
| d090 | Warning monitor | - | - | Displays the active warning code. |
| d102 | DC bus voltage monitor | 0.0 to 999.9 V | - | Internal DC bus voltage; useful for over-/under-voltage diagnosis. |
| d103 | BRD load ratio monitor | 0.0 to 100.0 % | - | How heavily the built-in brake chopper is being used. |
| d104 | Electronic thermal monitor | 0.0 to 100.0 % | - | Accumulated motor thermal load; an E05 trip is expected as this approaches full. Available from version 3.0. |
| F001 | Output frequency setting | 0.0 / start freq. to A004 Hz | 0.00 | Target frequency used when the frequency source is set to the keypad value (A001 = 02). |
| F002 | Acceleration time (1) | 0.00 to 3600 s | 10.00 | Ramp-up time of the standard (first) acceleration profile. |
| F202 | Acceleration time (1), 2nd motor | 0.00 to 3600 s | 10.00 | Same as F002 but applied when the second motor set is selected. |
| F003 | Deceleration time (1) | 0.00 to 3600 s | 10.00 | Ramp-down time of the standard (first) deceleration profile. Lengthen it to cure over-voltage trips. |
| F203 | Deceleration time (1), 2nd motor | 0.00 to 3600 s | 10.00 | Second-motor version of F003. |
| F004 | Keypad RUN key direction | 00 Forward / 01 Reverse | 00 | Chooses which direction the RUN key on the keypad commands. |
| A001 | Frequency source | 00 POT, 01 Terminal, 02 F001, 03 Modbus, 04 Option, 06 Pulse train, 07 EzSQ, 10 Calculate | 01 | Selects where the speed reference comes from. If the drive ignores the keypad or analog input, check this first. |
| A201 | Frequency source, 2nd motor | as A001 | 01 | Second-motor version of A001. |
| A002 | Run command source | 01 Terminal, 02 Keypad RUN, 03 Modbus, 04 Option | 01 | Selects where start/stop commands come from. A drive that will not start from the keypad usually has this set to terminal. |
| A202 | Run command source, 2nd motor | as A002 | 01 | Second-motor version of A002. |
| A003 | Base frequency | 30 Hz to A004 | 50.0 | Frequency at which the output reaches full voltage; set to match the motor nameplate. |
| A203 | Base frequency, 2nd motor | 30 Hz to A204 | 50.0 | Second-motor version of A003. |
| A004 | Maximum frequency | base freq. to 400 (580) Hz | 50.0 | Upper limit of the output frequency for the V/f pattern and reference scaling. |
| A204 | Maximum frequency, 2nd motor | 2nd base freq. to 400 (580) Hz | 50.0 | Second-motor version of A004. |
| A005 | [AT] selection | 00, 02, 03 | 00 | Defines which analog inputs the AT terminal switches between (O/OI, O/POT or OI/POT). |
| A011 | [O] input start frequency | 0.00 to 400.0 (580.0) Hz | 0.00 | Frequency corresponding to the bottom of the 0-10 V analog input range. |
| A012 | [O] input end frequency | 0.00 to 400.0 (580.0) Hz | 0.00 | Frequency corresponding to the top of the 0-10 V input range. |
| A013 | [O] input start voltage | 0. to 100. % | 0. | Percentage of the voltage input at which the active range begins. |
| A014 | [O] input end voltage | 0. to 100. % | 100. | Percentage of the voltage input at which the active range ends. |
| A015 | [O] start frequency enable | 00 Use A011, 01 Use 0 Hz | 01 | Chooses whether the output at the minimum analog signal is the A011 offset or 0 Hz. |
| A016 | Analog input filter | 1 to 31 | 8. | Smoothing filter for analog inputs; higher values calm a noisy reference but respond slower. |
| A019 | Multi-speed operation selection | 00 Binary, 01 Bit | 00 | Chooses binary (16 speeds from 4 terminals) or bit-wise (8 speeds) multi-speed selection. |
| A020 | Multi-speed frequency 0 | 0.00 / start freq. to 400 (580) Hz | 6.0 | First preset speed. Presets 1-15 are A021 to A035. |
| A021-A035 | Multi-speed frequency 1 to 15 | 0.00 / start freq. to 400 (580) Hz | 0.0 | Fifteen further preset speeds selected by the CF terminals. |
| A038 | Jog frequency | start freq. to 9.99 Hz | 6.00 | Speed used for jogging. |
| A039 | Jog stop mode | 00-05 | 04 | How the motor stops at the end of a jog (free-run, controlled decel or DC brake, with or without operation during run). |
| A041 | Torque boost select | 00 Manual, 01 Automatic | 00 | Chooses fixed or automatic low-speed torque boost. |
| A042 | Manual torque boost value | 0.0 to 20.0 % | 1.0 | Extra voltage at low speed to help starting; too much can cause over-current trips. |
| A043 | Manual torque boost frequency | 0.0 to 50.0 % | 5.0 | Frequency point (as a percentage of base) at which the manual boost ends. |
| A044 | V/f characteristic curve | 00 Constant torque, 01 Reduced torque, 02 Free V/f, 03 SLV | 00 | Selects the voltage/frequency pattern or sensorless vector control. |
| A045 | V/f gain | 20. to 100. % | 100. | Scales the output voltage of the chosen V/f pattern. |
| A051 | DC braking enable | 00 Off, 01 During stop, 02 Frequency detection | 00 | Turns on DC injection braking at stop. |
| A052 | DC braking frequency | B082 to 60 Hz | 0.5 | Frequency below which DC braking begins. |
| A053 | DC braking wait time | 0.0 to 5.0 s | 0.0 | Delay between end of deceleration and start of DC braking. |
| A054 | DC braking force (decel) | 0 to 100 % | 50. | Strength of the DC braking current. |
| A055 | DC braking time (decel) | 0.0 to 60.0 s | 0.5 | How long DC braking is applied. |
| A056 | DC braking edge/level detect for [DB] | 00 Edge, 01 Level | 01 | Whether the DB terminal acts on a level or on an edge. |
| A057 | DC braking force at start | 0 to 100 % | 0. | DC braking level applied before starting to hold the shaft. |
| A058 | DC braking time at start | 0.0 to 60.0 s | 0.0 | Duration of the start-time DC braking. |
| A059 | Carrier frequency during DC braking | 2.0 to 15.0 kHz | 5.0 | PWM carrier used while DC braking (manual lists the unit as s; range implies kHz). |
| A061 | Frequency upper limit | A062 to A004 Hz (0.0 = off) | 0.00 | Caps the output below the maximum frequency. |
| A062 | Frequency lower limit | B082 to A061 Hz (0.0 = off) | 0.00 | Minimum frequency the drive will run at once started. |
| A063 | Jump frequency 1 (center) | 0.00 to 400.0 (580.0) Hz | 0.00 | Centre of a frequency band the drive skips to avoid mechanical resonance. A065 and A067 are jumps 2 and 3. |
| A064 | Jump frequency 1 width | 0.00 to 10.0 Hz | 0.50 | Half-width of jump band 1. A066 and A068 are widths 2 and 3. |
| A069 | Acceleration hold frequency | 0.0 to 400.0 (580.0) Hz | 0.00 | Frequency at which acceleration pauses. |
| A070 | Acceleration hold time | 0.0 to 60.0 s | 0.0 | Duration of the acceleration pause. |
| A071 | PID enable | 00 Off, 01 On, 02 On with reverse | 00 | Turns on the built-in PID controller. |
| A072 | PID proportional gain | 0.00 to 25.00 | 1.00 | Proportional gain of the PID loop. |
| A073 | PID integral time | 0.0 to 3600 s | 1.0 | Integral time constant. |
| A074 | PID derivative time | 0.00 to 100.0 s | 0.00 | Derivative time constant. |
| A075 | PV scale conversion | 0.01 to 99.99 | 1.00 | Multiplier applied to the feedback value for display. |
| A076 | PV source | 00 OI, 01 O, 02 Modbus, 03 Pulse, 10 Calculate | 00 | Chooses the feedback signal for PID. |
| A077 | Reverse PID action | 00 SP-PV, 01 -(SP-PV) | 00 | Inverts the error sign for processes where more output lowers the feedback. |
| A078 | PID output limit | 0.0 to 100.0 % | 0.0 | Limits how much the PID output can correct the frequency. |
| A081 | AVR function select | 00 On, 01 Off, 02 On except decel | 02 | Automatic voltage regulation keeps motor voltage steady when supply varies. |
| A082 | AVR voltage select | 200V: 200-240; 400V: 380-480 V | 230/400 | Rated motor voltage for AVR; set from the motor nameplate. |
| A085 | Energy-saving operation mode | 00 Normal, 01 Energy-saving | 00 | Reduces output voltage under light load to save energy. |
| A092 | Acceleration time (2) | 0.00 to 3600 s | 10.00 | Second acceleration ramp time. |
| A093 | Deceleration time (2) | 0.00 to 3600 s | 10.00 | Second deceleration ramp time. |
| A094 | Method to switch to Acc2/Dec2 | 00 2CH terminal, 01 Frequency, 02 FWD/REV | 00 | Chooses what triggers the second ramp set. |
| A095 | Acc1 to Acc2 transition frequency | 0.00 to 400.0 (580.0) Hz | 0.00 | Frequency at which acceleration changes to the second ramp. |
| A096 | Dec1 to Dec2 transition frequency | 0.00 to 400.0 (580.0) Hz | 0.00 | Frequency at which deceleration changes to the second ramp. |
| A097 | Acceleration curve selection | 00-04 | 01 | Ramp shape for acceleration: linear, S, U, inverse U or EL-S. |
| A098 | Deceleration curve selection | 00-04 | 01 | Ramp shape for deceleration. |
| A101 | [OI] input start frequency | 0.00 to 400.0 (580.0) Hz | 0.00 | Frequency at the bottom of the 4-20 mA input range. |
| A102 | [OI] input end frequency | 0.00 to 400.0 (580.0) Hz | 0.00 | Frequency at the top of the current input range. |
| A103 | [OI] input start current | 0. to 100. % | 20. | Percentage of full-scale current at which the active range starts (20% = 4 mA). |
| A104 | [OI] input end current | 0. to 100. % | 100. | Percentage of full-scale current at which the active range ends. |
| A105 | [OI] start frequency select | 00 Use A101, 01 Use 0 Hz | 00 | Whether output at minimum signal is A101 or 0 Hz. |
| A141 | A input select (calculate function) | 00-07 | 02 | First operand source for the calculate function. |
| A142 | B input select (calculate function) | 00-07 | 03 | Second operand source for the calculate function. |
| A143 | Calculation symbol | 00 ADD, 01 SUB, 02 MUL | 00 | Operation applied to A and B inputs. |
| A145 | ADD frequency | 0.00 to 400. (580.) Hz | 0.00 | Offset added to or subtracted from the output frequency when the ADD terminal is on. |
| b001 | Restart mode on power failure / under-voltage | 00-04 | 00 | Selects whether and how the drive restarts after a power dip. |
| b002 | Allowable under-voltage power failure time | 0.3 to 25 s | 1.0 | How long an under-voltage can last before the drive trips regardless of restart mode. |
| b003 | Retry wait time before motor restart | 0.3 to 100 s | 1.0 | Delay after power returns before the motor restarts. |
| b004 | Power failure / under-voltage trip alarm enable | 00, 01, 02 | 00 | Whether a brief power failure raises a trip alarm. |
| b005 | Number of restarts on power failure | 00 16 times, 01 always | 00 | Limits automatic restarts after under-voltage. |
| b008 | Restart mode on over-voltage / over-current trip | 00-04 | 00 | Automatic restart behaviour after OC/OV trips. |
| b010 | Number of retries on OV/OC trip | 1 to 3 times | 3 | Maximum automatic retries after over-voltage/over-current trips. |
| b011 | Retry wait time on OV/OC trip | 0.3 to 100 s | 1.0 | Wait before each retry. |
| b012 | Level of electronic thermal | 20 to 100 % of rated inverter current | Rated current of model | Motor overload trip level; set to the motor nameplate current to protect the motor (E05). |
| b013 | Electronic thermal characteristic | 00 Reduced torque, 01 Constant torque, 02 Free | 01 | Selects the thermal curve matching the motor type and cooling. |
| b015 | Free thermal frequency 1 | 0 to 400 (580) Hz | 0. | First frequency point for the free-setting thermal curve (b017, b019 are points 2 and 3; b016, b018, b020 are the currents). |
| b021 | Overload restriction operation mode | 00-03 | 01 | Limits current during overload by adjusting frequency instead of tripping. |
| b022 | Overload restriction level | 20 to 200 % of rated current | Rated current x 1.5 | Current level at which overload restriction acts. |
| b023 | Deceleration rate at overload restriction | 0.1 to 3000.0 s | 1.0 | How fast frequency is reduced during overload restriction. |
| b027 | OC suppression selection | 00 Off, 01 On, 02 On with voltage reduction | 00 | Suppresses over-current trips by easing the output. |
| b031 | Software lock mode selection | 00, 01, 02, 03, 10 | 01 | Locks parameters against changes. If a value will not change, check this and the SFT terminal. |
| b033 | Motor cable length parameter | 5. to 20. | 10. | Cable length compensation setting. |
| b034 | Run / power-on warning time | 0 to 655,350 h | 0. | Time after which a run-time warning is raised; 0 disables. |
| b035 | Rotation direction restriction | 00 None, 01 Reverse inhibited, 02 Forward inhibited | 00 | Blocks one direction of rotation. |
| b036 | Reduced voltage start selection | 0 to 255 | 2 | Softens the voltage ramp at start; 0 disables. |
| b037 | Function code display restriction | 00-05 | 00 | Restricts which parameters are visible; if a parameter seems missing set 00 for full display. |
| b038 | Initial display selection | 000, 001-030, 201, 202 | 001 | Chooses the parameter shown on power-up. |
| b040 | Torque limit selection | 00-02 | 00 | Chooses how torque limits are set (by quadrant, terminals or analog). |
| b041 | Torque limit 1 (fwd/power) | 0 to 200 % / no | 200. | Torque limit in the forward driving quadrant (b042-b044 cover the other quadrants). |
| b046 | Reverse run protection | 00 Off, 01 On | 00 | Prevents unintended reverse rotation. |
| b049 | Dual rating selection | 00 CT, 01 VT | 00 | Selects constant-torque or variable-torque drive rating. |
| b050 | Controlled deceleration on power loss | 00-03 | 00 | What the drive does when mains is lost: trip or ride through by decelerating. |
| b070 | Operation level at [O] disconnection | 0. to 100. % / no | no | Reference level the drive uses if the voltage analog signal is lost. |
| b071 | Operation level at [OI] disconnection | 0. to 100. % / no | no | Reference level used if the 4-20 mA signal is lost. |
| b075 | Ambient temperature setting | -10 to 50 C | 40 | Ambient temperature used for derating decisions. |
| b078 | Watt-hour clearance | 00 Off, 01 Clear | 00 | Clears the watt-hour counter. |
| b082 | Start frequency | 0.10 to 9.99 Hz | 0.50 | Frequency at which output starts when a run command is given. |
| b083 | Carrier frequency | 2.0 to 15.0 kHz | 10.0 | PWM switching frequency; lower it to cut noise and heating, raise it for quieter motor. |
| b084 | Initialization mode | 00-04 | 00 | Chooses what is reset: trip history, parameters, or both (and the EzSQ program). |
| b085 | Country for initialization | 01 Mode 1 | 01 | Regional default set used on initialization. |
| b086 | Frequency scaling conversion factor | 0.01 to 99.99 | 1.00 | Multiplier for the scaled frequency display d007. |
| b087 | STOP key enable | 00 On, 01 Always off, 02 Off for stop | 00 | Whether the keypad STOP key works. |
| b088 | Restart mode after FRS | 00-02 | 00 | How the drive resumes after a free-run stop is cancelled. |
| b089 | Automatic carrier frequency reduction | 00-02 | 01 | Reduces carrier automatically as current or heatsink temperature rises. |
| b090 | Dynamic braking usage ratio | 0.0 to 100 % | 0.0 | Allowed duty of the braking resistor; 0 disables braking (E06 threshold). |
| b091 | Stop mode selection | 00 Decel, 01 Free-run | 00 | Whether a stop command ramps down or coasts. |
| b092 | Cooling fan control | 00 Always, 01 During run, 02 Temperature | 01 | When the cooling fan runs. |
| b094 | Initialization target data | 00-03 | 00 | Which parameter groups are reset on initialization. |
| b095 | Dynamic braking control (BRD) selection | 00 Off, 01 Run only, 02 Always | 00 | Enables the built-in brake chopper. |
| b096 | BRD activation level | 200V: 330-390; 400V: 660-780 V | 360/720 | DC bus voltage at which braking turns on. |
| b097 | BRD resistor value | min. resistance to 600.0 ohm | Min. resistance | Value of the connected braking resistor. |
| b120 | Brake control enable | 00, 01, 02 | 00 | Enables the mechanical brake sequence. |
| b121 | Brake wait time for release | 0.00 to 5.00 s | 0.00 | Delay before the brake release signal. |
| b124 | Brake wait time for confirmation | 0.00 to 5.00 s | 0.00 | Time allowed for brake confirmation before an E36 trip. |
| b130 | Deceleration overvoltage suppression enable | 00 Off, 01 On, 02 On with accel | 00 | Prevents E07 trips by holding or extending deceleration when the DC bus rises. |
| b131 | Decel overvoltage suppression level | 200V: 330-395; 400V: 660-790 V | 380/760 | DC bus level at which suppression acts. |
| b145 | GS input mode | 00-06 | 00 | Selects how the safe stop (GS1/GS2) inputs behave and which trip codes they produce. |
| b150 | Display when external operator connected | d001-d030 | 001 | Parameter shown on the built-in display when an external operator is attached. |
| b165 | External operator communication loss action | 00-04 | 02 | What the drive does if the external operator connection is lost. |
| b166 | Data read/write select | 00 Read/Write, 01 Protected | 00 | Write protection for data. |
| b171 | Inverter mode selection | 00-03 | 00 | Selects standard IM, high-frequency IM or PM motor mode. Initialise after changing. |
| b180 | Initialization trigger | 00 Off, 01 Perform | 00 | Setting 01 starts the initialization configured by b084, b085 and b094. |
| b190 | Password setting A | 0000 to FFFF | 0000 | Sets a password for parameter protection. |
| b191 | Password authentication A | 0000 to FFFF | 0000 | Entry used to unlock password A. |
| C001 | Input [1] function | 68 options | 00 [FW] | Assigns a function to digital input terminal 1; C002-C007 do the same for terminals 2-7. |
| C002 | Input [2] function | 68 options | 01 [RV] | Function of input terminal 2. |
| C003 | Input [3] function | 68 options | 12 [EXT] | Function of input terminal 3 (can be GS1). |
| C004 | Input [4] function | 68 options | 18 [RS] | Function of input terminal 4 (can be GS2). |
| C005 | Input [5] function | 68 options | 02 [CF1] | Function of input terminal 5 (can be PTC thermistor). |
| C006 | Input [6] function | 68 options | 03 [CF2] | Function of input terminal 6. |
| C007 | Input [7] function | 68 options | 06 [JG] | Function of input terminal 7. |
| C011 | Input [1] active state | 00 NO, 01 NC | 00 | Normally open or closed logic for input 1; C012-C017 cover inputs 2-7. |
| C021 | Output [11] function | 48 options | 00 [RUN] | Function of open-collector output 11. |
| C022 | Output [12] function | 48 options | 01 [FA1] | Function of open-collector output 12. |
| C026 | Alarm relay function | 48 options | 05 [AL] | Function of the relay output. |
| C027 | [EO] terminal selection | 00-16 | 07 | Signal output on the pulse/PWM EO terminal. |
| C028 | [AM] terminal selection | 00-16 | 07 [LAD] | Signal output on the 0-10 V AM terminal. |
| C031 | Output [11] active state | 00 NO, 01 NC | 00 | Contact logic of output 11. |
| C032 | Output [12] active state | 00 NO, 01 NC | 00 | Contact logic of output 12. |
| C036 | Alarm relay active state | 00 NO, 01 NC | 01 | Relay logic; default NC means the relay also signals power loss. |
| C039 | Low current detection level | 0.0 to 2.0 x rated current | Rated current | Threshold for the low-load output. |
| C041 | Overload warning level | 0 to 2 x rated current | Rated current x 1.15 | Current at which the OL output turns on, before an overload trip. |
| C042 | Frequency arrival setting for acceleration | 0.0 to 400.0 (580.0) Hz | 0.00 | Threshold for the FA2/FA3 outputs during acceleration. |
| C043 | Frequency arrival setting for deceleration | 0.0 to 400.0 (580.0) Hz | 0.00 | Threshold for the FA2/FA3 outputs during deceleration. |
| C061 | Electronic thermal warning level | 0 to 100 % | 90. | Thermal load at which the THM warning output turns on. |
| C063 | Zero speed detection level | 0.00 to 100.0 Hz | 0.00 | Frequency below which the ZS output is on. |
| C064 | Heat sink overheat warning | 0. to 110. C | 100. | Heatsink temperature at which the OHF warning output turns on. |
| C071 | Communication speed | 03-10 | 05 | Modbus baud rate (05 = 9600). Power cycle needed. |
| C072 | Modbus address | 1 to 247 | 1. | Slave address of the drive on the network. |
| C074 | Communication parity | 00 None, 01 Even, 02 Odd | 00 | Serial parity. Power cycle needed. |
| C075 | Communication stop bit | 1 or 2 | 1 | Number of stop bits. Power cycle needed. |
| C076 | Communication error select | 00-04 | 02 | Action on a communication error: trip, decelerate, ignore, coast or decelerate to stop (trip gives E41). |
| C077 | Communication error time-out | 0.00 to 99.99 s | 0.00 | Watchdog time before a communication loss is declared. |
| C078 | Communication wait time | 0. to 1000. ms | 0. | Delay before the drive replies to a Modbus request. |
| C081 | [O] input span calibration | 0.0 to 200.0 % | 100.0 | Fine scale adjustment of the voltage analog input. |
| C082 | [OI] input span calibration | 0.0 to 200.0 % | 100.0 | Fine scale adjustment of the current analog input. |
| C085 | Thermistor input span calibration | 0.0 to 200.0 % | 100.0 | Calibration for the PTC thermistor input. |
| C096 | Communication selection | 00 Modbus-RTU, 01 EzCOM, 02 EzCOM admin | 00 | Serial protocol used on RS-485. Power cycle needed. |
| C101 | Up/Down memory mode selection | 00 Clear, 01 Keep | 00 | Whether the UP/DWN adjusted frequency is remembered after power-off. |
| C102 | Reset selection | 00-03 | 00 | Defines when the RS input clears a trip and whether it stops a running drive. |
| C103 | Restart mode after reset | 00-02 | 00 | How the drive restarts after a reset. |
| C111 | Overload warning level 2 | 0 to 2 x rated current | Rated current x 1.15 | Threshold for the second overload warning output (OL2). |
| C160 | Input [1] response time | 0 to 200 (x2 ms) | 1. | Debounce/response time of input 1; C161-C166 for inputs 2-6. |
| H001 | Auto-tuning selection | 00 Off, 01 Stopped, 02 Rotating | 00 | Starts motor auto-tuning to measure motor constants. |
| H002 | Motor constant selection | 00 Hitachi standard, 02 Auto-tuned | 00 | Chooses which motor data set the drive uses. |
| H003 | Motor capacity | 0.1 to 18.5 kW | Model dependent | Motor power; set from the nameplate. |
| H004 | Motor poles setting | 2 to 48 poles | 4 | Number of motor poles; set from nameplate. |
| H005 | Motor speed response constant | 1 to 1000 | 100. | Speed response gain for vector control. |
| H006 | Motor stabilization constant | 0. to 255. | 100. | Stability adjustment; raise if the motor hunts. |
| H020 | Motor constant R1 (Hitachi motor) | 0.001 to 65.535 ohm | Model dependent | Primary resistance for standard Hitachi motor data; H021 R2, H022 L, H023 I0, H024 J follow. |
| H030 | Motor constant R1 (auto-tuned) | 0.001 to 65.535 ohm | Model dependent | Auto-tuned primary resistance; H031 R2, H032 L, H033 I0, H034 J follow. |
| H102 | PM motor code setting | 00 Hitachi standard, 01 Auto-tune | 00 | Selects PM motor data source. |
| H103 | PM motor capacity | 0.1 to 18.5 kW | kW dependent | Rated power of the PM motor. |
| H104 | PM motor pole setting | 2 to 48 | kW dependent | Number of poles of the PM motor. |
| H105 | PM rated current | 0.00 to 1.00 x inverter rated current | kW dependent | Rated current of the PM motor. |
| P001 | Reaction when option card error occurs | 00 Trip, 01 Ignore | 00 | Whether an option card fault trips the drive. |
| P003 | [EA] terminal selection | 00, 01, 02 | 00 | Function of the EA input (speed reference, encoder feedback or EzSQ). |
| P004 | Pulse train input mode for feedback | 00-03 | 00 | Encoder signal type. |
| P011 | Encoder pulse setting | 32 to 1024 ppr | 512 | Encoder pulses per revolution. |
| P026 | Over-speed error detection level | 0 to 150 % | 115.0 | Level used for the E81 excessive speed trip. |
| P027 | Speed deviation error detection level | 0 to 120 Hz | 10.00 | Speed deviation threshold for DSE output. |
| P200 | Serial communication mode | 00 Standard, 01 Free mapping | 00 | Select Modbus register mapping mode. Power cycle needed. Version 3.0 onwards. |
See also the Hitachi WJ200 fault codes. ServMod reads, compares and backs up these parameters from your phone: how to connect.
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.