CodeNameMeaning
E01Over-current at constant speedOutput current went above the safe limit while the drive was running at steady speed (short circuit, locked...
E02Over-current during decelerationExcess output current was detected while slowing down; output is cut. The manual gives the same cause hints...
E03Over-current during accelerationExcess output current was detected while speeding up; output is cut. Same cause hints as E01.
E04Over-current in other conditionsOver-current occurred at a time that is not constant speed, acceleration or deceleration. Same cause hints as...
E05Motor overload (electronic thermal)The drive's electronic thermal model decided the motor was overloaded and tripped the output.
E06Braking resistor overloadThe braking-chopper duty ratio went above the limit set in b090, so the drive shut off its output.
E07Over-voltageThe DC bus voltage rose above its limit, for example from regenerative energy from the motor or a high supply...
E08EEPROM errorThe built-in memory had a problem, typically due to noise or high temperature, and the output was shut off.
E09Under-voltageThe internal DC bus voltage dropped under its threshold, which can cause control faults, motor heating or...
E10Current detection errorA fault in the drive's internal current sensing circuit was detected and the output was shut off.
E11CPU errorThe drive's processor malfunctioned and the output was switched off.
E12External tripA digital input assigned to the EXT function (option 12) was activated, so the drive latched a trip.
E13Unattended start protection (USP)Power was applied while a run command was already active and USP was enabled, so the drive refused to start.
E14Ground faultA ground fault between the drive output and the motor was found during the power-up test. This protects the...
E15Input over-voltageThe drive checks incoming voltage after 100 seconds in stop mode and tripped because the level was too high.
E19Inverter thermal sensor errorThe thermal sensor inside the power module is not connected / not being read.
E21Inverter over-temperatureThe temperature of the power devices went above the allowed level, so the drive tripped.
E22CPU communication errorCommunication between the drive's two processors failed.
E25Main circuit errorThe drive could not confirm that its main power supply circuit was established, because of noise or a damaged...
E30Driver errorA fault in the safety protection circuit between the CPU and the output driver was detected, possibly from...
E35Thermistor tripThe motor thermistor connected to terminals 5 and L indicated an over-temperature, so the output was turned...
E36Brake errorWith brake control enabled (b120 = 01) the drive did not receive the brake confirmation signal within the...
E37Safe stopThe safe-stop (GS) input was triggered when b145 is set to 01.
E38Low-speed overloadThe drive detected an overload while running at very low speed and shut off the output.
E40Operator connection errorCommunication between the drive and its keypad/operator failed.
E41Modbus communication errorA Modbus timeout occurred while the communication error action was set to trip (C076 = 00).
E43EzSQ invalid instructionThe stored EzSQ program is corrupt, or the PRG input was turned on when no program was downloaded.
E44EzSQ nesting count errorIn the EzSQ program, subroutines, if-statements or for-next loops are nested deeper than eight levels.
E45EzSQ instruction errorThe drive met a program instruction it cannot execute.
E50-E59EzSQ user trip 0 to 9User-defined trips raised by the EzSQ program (E50 to E59 correspond to user trip 0 to 9).
E60-E69Option board errorThe drive detected an error in the option board fitted in the option slot.
E80Encoder disconnectionAn encoder connection error was found: broken wiring, failed encoder, or an encoder that does not support...
E81Excessive speedMotor speed reached or exceeded the maximum frequency (A004) multiplied by the over-speed detection level...
E83Positioning range errorThe current position went outside the allowed position range set by P072 and P073.
E98Outside failure (safe stop)Raised from the safe stop signal when b145 = 02 (outside failure).
E99Inside failure (safe stop)Raised from the safe stop signal when b145 = 02, 03 or 05 (inside failure).

Source: WJ200 Series Quick Reference Guide (NT3381AX, April 2016). Manufacturer page. See also the Hitachi WJ200 parameter list, the connection and backup page and the wiring diagrams.

Download free for Android

This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.