ServMod Sign in

Fault codes / Hitachi WJ200 / E07

Hitachi WJ200 fault E07: Over-voltage

The DC bus voltage rose above its limit, for example from regenerative energy from the motor or a high supply voltage.

What to check

  1. Lengthen the deceleration time or enable deceleration over-voltage suppression (b130)
  2. Fit or check a braking resistor / unit for overhauling loads
  3. Measure the incoming supply voltage for surges or an over-high level

Source: WJ200 Series Quick Reference Guide (NT3381AX, April 2016), page 98. Manufacturer page.

Keep the settings safe before you change anything

Before you reset, replace or reprogram a Hitachi WJ200, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Hitachi WJ200 to a phone and the wiring diagrams.

Download free for Android

Other Hitachi WJ200 fault codes

E01E02E03E04E05E06E07E08E09E10E11E12E13E14E15E19E21E22E25E30E35E36E37E38E40E41E43E44E45E50-E59E60-E69E80E81E83E98E99

This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.