Fault codes / Hitachi WJ200 / E09
Hitachi WJ200 fault E09: Under-voltage
The internal DC bus voltage dropped under its threshold, which can cause control faults, motor heating or weak torque. The drive shuts off its output.
What to check
- Measure the supply voltage on all phases and look for dips or a missing phase
- Check input contactor, fuses, terminals and any input reactor
- See restart-after-undervoltage settings b001 to b005
Source: WJ200 Series Quick Reference Guide (NT3381AX, April 2016), page 98. Manufacturer page.
Keep the settings safe before you change anything
Before you reset, replace or reprogram a Hitachi WJ200, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Hitachi WJ200 to a phone and the wiring diagrams.
Other Hitachi WJ200 fault codes
E01E02E03E04E05E06E07E08E09E10E11E12E13E14E15E19E21E22E25E30E35E36E37E38E40E41E43E44E45E50-E59E60-E69E80E81E83E98E99
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.