ServMod Sign in

Fault codes / Hitachi WJ200 / E02

Hitachi WJ200 fault E02: Over-current during deceleration

Excess output current was detected while slowing down; output is cut. The manual gives the same cause hints as E01.

What to check

  1. Look for a shorted motor lead or phase-to-phase / phase-to-earth fault: disconnect the motor and megger the cable and motor windings
  2. Check that the motor shaft turns freely and the load is not jammed or overloaded
  3. On a dual-voltage motor, confirm the star/delta link arrangement matches the supply voltage
  4. Lengthen the deceleration time (F003 / A093) if the load inertia is high

Source: WJ200 Series Quick Reference Guide (NT3381AX, April 2016), page 98. Manufacturer page.

Keep the settings safe before you change anything

Before you reset, replace or reprogram a Hitachi WJ200, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Hitachi WJ200 to a phone and the wiring diagrams.

Download free for Android

Other Hitachi WJ200 fault codes

E01E02E03E04E05E06E07E08E09E10E11E12E13E14E15E19E21E22E25E30E35E36E37E38E40E41E43E44E45E50-E59E60-E69E80E81E83E98E99

This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.