Fault codes / Hitachi WJ200 / E01
Hitachi WJ200 fault E01: Over-current at constant speed
Output current went above the safe limit while the drive was running at steady speed (short circuit, locked rotor or heavy load). Output is switched off.
What to check
- Look for a shorted motor lead or phase-to-phase / phase-to-earth fault: disconnect the motor and megger the cable and motor windings
- Check that the motor shaft turns freely and the load is not jammed or overloaded
- On a dual-voltage motor, confirm the star/delta link arrangement matches the supply voltage
Source: WJ200 Series Quick Reference Guide (NT3381AX, April 2016), page 98. Manufacturer page.
Keep the settings safe before you change anything
Before you reset, replace or reprogram a Hitachi WJ200, save all its parameters to your phone with ServMod, so a replacement can be set up in minutes. See how to connect the Hitachi WJ200 to a phone and the wiring diagrams.
Other Hitachi WJ200 fault codes
E01E02E03E04E05E06E07E08E09E10E11E12E13E14E15E19E21E22E25E30E35E36E37E38E40E41E43E44E45E50-E59E60-E69E80E81E83E98E99
This is a short summary written by ServMod. It can contain mistakes or be out of date. Check the manufacturer's current manual before changing settings or opening a drive. ServMod is independent and is not made, approved or supported by the manufacturer. Work on live equipment only if you are qualified, and isolate and lock out the supply first.